Section 2 Controller Troubleshooting
Fault or Event Message
See
Section
Check
Possible Cause
Module Status Change
A new accessory module is
detected
Press the reset button to open Reset
New Module screen. Then press Reset
again.
2.7.2
A module has been disconnected
Check connections from the controller
to the I/O module assembly and at the
top of each I/O module.
Verify that the module is securely
installed.
If a module has been removed, go to
Set Inputs/Outputs screen and uninstall
the module.
2.7.2
Communication to an installed I/O
module has been lost
Check I/O module connections.
2.7.2
Real-time clock failure on logic
board
If the procedures in Section 2.7.2 fail to
clear the error message, replace the
controller’s logic board.
2.7.2
4.14
Module Status Conflict
One type of module was replaced
with another type of module that
has the same address
Follow the procedure in Section 2.7.3 to
uninstall the old module and then install
the new module.
2.7.3
External Fault
Fault condition in customer-
supplied equipment connected to
external input
Identify and correct the cause of the
fault condition.
Manuals
for
connected
equipment
Looose or faulty connection
Check connection to external input.
ATS OIM
Summary of Contents for KGP
Page 2: ......
Page 6: ...TP 6461 1 08 6 Notes ...
Page 10: ...TP 6461 1 08 10 Safety Precautions and Instructions Notes ...
Page 22: ...TP 6461 1 08 22 Section 1 Scheduled Maintenance Notes ...
Page 36: ...TP 6461 1 08 36 Section 2 Controller Troubleshooting Notes ...
Page 54: ...TP 6461 1 08 54 Section 3 Transfer Switch Troubleshooting Notes ...
Page 78: ...TP 6461 1 08 78 Section 4 Controller Test and Replacement Notes ...
Page 86: ...TP 6461 1 08 86 Section 5 Component Replacement Model KGS KGP Notes ...
Page 100: ...TP 6461 1 08 100 Section 6 Component Replacement Model KSS Switches Notes ...
Page 125: ......