TP-6461 1/08
70
Section 4 Controller Test and Replacement
4.9
Calibration
Hazardous voltage.
Will cause severe injury or death.
Only authorized personnel should
open the enclosure.
DANGER
Testing live electrical circuits.
Hazardous voltage or
current can cause severe injury or death.
Have trained and
qualified personnel take diagnostic measurements of live
circuits. Use adequately rated test equipment with electrically
insulated probes and follow the instructions of the test
equipment manufacturer when performing voltage tests.
Observe the following precautions when performing voltage
tests: (1) Remove all jewelry. (2) Stand on a dry, approved
electrically insulated mat. (3) Do not touch the enclosure or
components inside the enclosure. (4) Be prepared for the
system to operate automatically.
(600 volts and under)
The transfer switch controls are calibrated at the factory
and should not require recalibration in the field.
However, if recalibration is necessary, measure the
source voltages as instructed in Section 3.3.2, record
the
measured
values,
and
use
the
Setup
Screen--Calibration to enter the measured values. See
Figure 4-15.
The current sensing accessory is required in order for
the transfer switch to measure and display the current
values.
Use a clamp-on current sensing meter to
measure the current and enter the measured values
through the Setup Screen--Calibration shown below.
Calibrate
L - N Voltages
Source N(E)
B
Y
"
Back
Back
Save
L1 - L0 VAC ###
Cal VAC ? ? ?
Calibration
B
Y
"
Main
Calibrate
L - L Voltages
Source N(E)
B
Y
"
Back
Back
Save
L1 - L2 VAC ###
Cal VAC ? ? ?
Calibrate
L1 - L2 Voltage
B
Y
"
Back
Calibrate
L1 - L0 Voltage
B
Y
"
Back
Calibrate
Load Current
B
Y
"
Back
Back
Save
LA Amps ####
Cal Amps ? ? ? ?
Calibrate
LA Current
B
Y
"
Back
Figure 4-15
Calibration
Summary of Contents for KGP
Page 2: ......
Page 6: ...TP 6461 1 08 6 Notes ...
Page 10: ...TP 6461 1 08 10 Safety Precautions and Instructions Notes ...
Page 22: ...TP 6461 1 08 22 Section 1 Scheduled Maintenance Notes ...
Page 36: ...TP 6461 1 08 36 Section 2 Controller Troubleshooting Notes ...
Page 54: ...TP 6461 1 08 54 Section 3 Transfer Switch Troubleshooting Notes ...
Page 78: ...TP 6461 1 08 78 Section 4 Controller Test and Replacement Notes ...
Page 86: ...TP 6461 1 08 86 Section 5 Component Replacement Model KGS KGP Notes ...
Page 100: ...TP 6461 1 08 100 Section 6 Component Replacement Model KSS Switches Notes ...
Page 125: ......