Section 2 Installation
For units with hinged doors, open the door and
disconnect the cable plug that connects the front door
components to the internal components. Disconnect
the grounding wire between the door and the enclosure.
Squeeze the release pins on each hinge together and
remove the door. See Figure 2-6. Set the door out of the
way to protect the controls.
Vertically mount 30- through 400-amp transfer switches
to a wall or other rigid vertical supporting structure. Use
the template on the shipping carton to locate the
mounting holes in the wall. Level the template before
marking and drilling the holes. Clearance holes through
the back of each enclosure are provided for mounting.
Use shims to plumb the enclosure. Verify that the door
hinges are vertical to avoid distortion of the enclosure or
door.
Bolt
600-
through
4000-amp
automatic
transfer
switches directly to floor mounting pads. Shim the
enclosure so that the enclosure is plumb.
2.4 Manual Operation Check
Hazardous voltage.
Will cause severe injury or death.
Disconnect all power sources before
opening the enclosure.
DANGER
Note:
A manual operation handle is provided on the
transfer switch
for maintenance purposes only
. Do
not use the manual operation handle to transfer
the load with the power connected.
Use the manual operation handle to check the manual
operation before energizing the transfer switch.
On
programmed-transition models, check the operation of
both the Normal and Emergency operators. Use the
following manual operation procedures to verify that the
contactor operates smoothly without binding.
Note:
A contactor in normal and serviceable condition
operates smoothly without binding. Do not place
the transfer switch into service if the contactor
does
not
operate
smoothly;
contact
an
authorized distributor/dealer to service the
contactor.
1
6126
1. Hinge release pins
Figure 2-6
Hinge
2.4.1
Manual Operation, 30--200 Amp
Open-Transition Switches
The 30--200 amp open-transition models have an
attached manual operating handle. See Figure 2-7.
Manual Operation Test Procedure, 30--200 Amp
Transfer Switches
1. Turn the attached handle to manually operate the
transfer switch. It should operate smoothly without
any binding. If it does not, check for shipping
damage or construction debris.
2. Return the transfer switch to the Normal position.
1
127a
1. Handle
Figure 2-7
Manual Operation Handle, 30--200 Amp
Open-Transition Switches