TP-6126 8/02
51
Section 6 Accessories
GM22502-A
REF
44.5
REF
47.6
REF
47.6
REF
12.7
REF
33.3
63.5
165.1
114.3
25.4
215.9
9.5
234.4
(4)
7.1
REF
47.6
REF
34.9
REF
95.3
#10--32 TERMINALS TYP. (4)
6” LEAD LENGTH REF
(CHARGER BODY TO INSERTION END OF CONNECTOR)
RED LIGHT
GREEN LIGHT
+
--
+
--
FUSE HOLDER (2)
AGC--10 10A
FASTBLOW FUSE
Figure 6-19
Battery Charger
6.8.1
Battery Charger Connection
The battery charger is powered by the load side of the
transfer switch contactor through a factory-installed
wiring harness with a 9-pin inline connector. Verify that
the power to the ATS is disconnected before connecting
or disconnecting the 9-pin connector to the battery
charger.
Ring terminals for battery charger connections are
included with the battery charger.
The installing technician must supply the cable with
terminals between the battery charger and the battery.
Figure 6-21 provides details regarding cable length and
gauge. Using red cable for battery positive (+) and black
cable for battery negative (--) is strongly recommended.
Use the following procedure to connect the battery
charger.
GM22502
CONNECTOR PIN--OUT
PIN
WIRE
FUNCTION
1
1
NEUTRAL INPUT
2
2
208 VAC INPUT
3
--
--
4
3
240 VAC INPUT
5
--
--
6
4
480 VAC INPUT
7
6
EARTH GROUND
8
--
--
9
5
600 VAC INPUT
TERMINAL
INSERTION
END
Figure 6-20
Battery Charger Power Connection