TP-6126 8/02
A-63
Appendix
Ratings with Specific Manufacturers’ Circuit Breakers, continued
Switch
Molded-Case Circuit Breakers
Switch
Rating,
Amps
WCR, kA
RMS
Voltage,
Max.
Manufacturer
Type
Max. Size,
Amps
SGL4, SGP4, TB4, THLC4, TLB4
400
GE
SGLA, SGL6, SGP6, TB6
600
SKHA, SKL8, SKP8, TKL
800
CJD6, HHJD6, HHJXD6, HJD6, SCJD6, SHJD6
400
ITE
CLD6, HHJD6, HHLXD6, HLD6, SCLD6, SHLD6
600
ITE
CMD6, HMD6, HND6, MD6, MXD6, SCMD6, SHMD6, SMD6,
SND6
800
400
42
480
Square D
LC, LI
600
400
42
480
Square D
MH
800
HKD, KDC, LCL, Tri-Pac LA
400
Cutler-Hammer
HLD
600
Tri-Pac NB
800
ABB
S5
400
ABB
S6
800
Merlin Gerin
CJ600
600
GE
TB8
800
GE
Microversatrip TKL
1200
CLD6, HHLD6, HHLDX6, HLD6, SCLD6, SHLD6
600
480
ITE
CMD6, HMD6, SCMD6, SHMD6
800
480
ITE
CND6, HND6, SCND6, SHND6
1200
65
CPD6
1600
600
800
Square D
MH Series 2
1000
800
1000
Square D
SE (LS Trip), SEH (LS Trip)
2500
1000
1200
Tri-Pac NB
800
1200
600
Cutler-Hammer
Tri-Pac PB
1600
RDC
2500
ABB
S6
800
42
480
ABB
S7
1200
42
480
Merlin Gerin
CJ600
600
Merlin Gerin
CK1200
1200
* Open-transition models only
[
Programmed-transition models only
Environmental Specifications
Environmental Specifications
Operating
Temperature
--20
°
C to 70
°
C (--4
°
F to 158
°
F)
Storage
Temperature
--40
°
C to 70
°
C (--40
°
F to 158
°
F)
Humidity
5% to 95% noncondensing
Altitude
0 to 3050 m (10000 ft.) without derating