TP-6071 3/00
42
Section 8 Component Troubleshooting
Refer to Figure 8-6 for troubleshooting information on the remote start panels.
Component
Ohmmeter
Connections
Procedure
Results
Remote start/stop switch
Remote switch: yellow/red wire
terminal and black wire terminal.
Place the ohmmeter on the R x 1
scale.
Press the rocker switch to the
START position.
Continuity—the switch is
functional. Open—replace
switch.
Remote switch: grey/black wire
terminal and black wire terminal.
Place the ohmmeter on the R x 1
scale.
Press the rocker switch to the
STOP position.
Continuity—the switch is
functional.
Genset ON light, gauge lights,
DC voltmeter, and hourmeter
Connect the red test lead to P3-4
and black test lead to P3-1.
Place the controller rocker switch
to the START position. Stop the
generator set when the test is
complete.
Generator set does not need to
be running, just cranking for this
test.
Note:
If the hourmeter is not
illuminated, test it by connecting
it to a 12-volt battery.
Note:
The hourmeter is polarity
sensitive.
If 12-volts DC is present and the
component does not function
after the J3 is connected to the
controller P3, replace the
component(s).
Water temperature gauge
Connect the red test lead to P3-4
(socket side) and black test lead
to P3-2 (socket side).
Start the generator set for the
test.
If 0.5--12-volts DC is present and
the gauge does not function after
the J3 is connected to
controller—replace the gauge.
Oil pressure gauge
Connect the red test lead to P3-4
(socket side) and black test lead
to P3-3 (socket side).
Start the generator set for the
test.
If 0.5--12-volts DC is present and
the gauge does not function after
the J3 is connected to the
controller—replace the gauge.
Note: Check continuity of gauge wiring and extension harness before replacing components.
Figure 8-6
Remote Start Panels Troubleshooting
Summary of Contents for 11.5EFOZ
Page 2: ......
Page 4: ...TP 6071 3 00 Table of Contents...
Page 10: ...TP 6071 3 00 VI Safety Precautions and Instructions Notes...
Page 18: ...TP 6071 3 00 6 Section 1 Specifications Notes...
Page 26: ...TP 6071 3 00 14 Section 4 Fuel System Notes...
Page 50: ...TP 6071 3 00 38 Section 7 Generator Troubleshooting Notes...
Page 60: ...TP 6071 3 00 48 Section 9 Generator Disassembly Reassembly Notes...
Page 66: ...TP 6071 3 00 54 Section 10 Wiring Diagrams Notes...
Page 67: ...TP 6071 3 00 55 Section 10 Wiring Diagrams 10 6 Wiring Diagram 4 Lead 229937 C...
Page 68: ...TP 6071 3 00 Section 10 Wiring Diagrams 56 10 7 Wiring Diagram 12 Lead 229938 A...