TP-6071 3/00
36
Section 7 Generator Troubleshooting
F+
F--
AC
AC
AC
TP-5983-7
1
2
5
4
6
7
8
3
1. Main field (rotor)
2. Stator windings
3. Frame connection
4. Shaft connection
5. Rectifier module
6. Megohmmeter
7. Armature
8. Exciter field
Figure 7-13
Megohmmeter Connections on
Main Field
7.11 Stator
The stator consists of a series of coils of wire laid in a
laminated steel frame. The stator leads supply voltage
to the AC load and exciter regulator.
Before testing the stator, inspect it for heat discoloration
and visible damage to the housing lead wires and
exposed and varnished areas of the frame laminations.
Be sure the stator is securely fastened in the stator
housing.
The stator produces electrical output (AC) as the
magnetized main field rotates within the stator windings.
Test the condition of the stator according to the following
procedure.
Leads 1, 2, 3, and 4 are the generator output leads.
Leads 55 and 66 are the voltage regulator supply and
sensing leads. The output of leads B1 and B2 is rectified
by BR1 to supply the control voltage. BR1 is located on
the controller circuit board. Refer to the schematic in
Figure 7-14 when performing the following tests.
Stator Test Procedure:
1. Place the start/stop switch in the STOP position.
2. Disconnect the generator set engine starting
battery, negative (--) lead first.
3. Check the generator output lead connections. See
Section 10, Wiring Diagrams.
F+
F--
AC
AC
AC
TP-5588-7
F1
F2
33
3
55
44
4
1
2
B1
B2
1
2
3
4
5
6
1. Main field (rotor)
2. Stator windings
3. Rectifier module
4. Ohmmeter
5. Armature
6. Exciter field
Figure 7-14
Stator Ohmmeter Connections
4. Disconnect all the stator leads to isolate the
windings. To check the stator continuity, set the
ohmmeter on the R x 1 scale. Check the stator
continuity by connecting the meter leads to the
stator leads as shown in Figure 7-14.
See
Figure 7-15 for single-phase and Figure 7-16 for
three-phase values. Perform the stator tests on all
the stator windings.
Between leads
Continuity
1 and 2
3 and 4
55 and 66
B1 and B2
1 and 3, 4, 33, 44
1 and 55, B1, and B2
4 and B1 and B2
55 and B1 and B2
Any stator lead and
ground
Yes
Yes
Yes
Yes
No
No
No
No
No
Figure 7-15
Stator Continuity 1-Phase
Summary of Contents for 11.5EFOZ
Page 2: ......
Page 4: ...TP 6071 3 00 Table of Contents...
Page 10: ...TP 6071 3 00 VI Safety Precautions and Instructions Notes...
Page 18: ...TP 6071 3 00 6 Section 1 Specifications Notes...
Page 26: ...TP 6071 3 00 14 Section 4 Fuel System Notes...
Page 50: ...TP 6071 3 00 38 Section 7 Generator Troubleshooting Notes...
Page 60: ...TP 6071 3 00 48 Section 9 Generator Disassembly Reassembly Notes...
Page 66: ...TP 6071 3 00 54 Section 10 Wiring Diagrams Notes...
Page 67: ...TP 6071 3 00 55 Section 10 Wiring Diagrams 10 6 Wiring Diagram 4 Lead 229937 C...
Page 68: ...TP 6071 3 00 Section 10 Wiring Diagrams 56 10 7 Wiring Diagram 12 Lead 229938 A...