![Kobold ZOK-ExK Operating Manual Download Page 48](http://html.mh-extra.com/html/kobold/zok-exk/zok-exk_operating-manual_1982351048.webp)
ZOK-E/-Z
Page 48
ZOK K14/0917
10.7.2 Switching
Output/
Output 1+2 / Source
With "Source" parameter, the source of the switching output can be assigned to the
"Input type" set in "Signal input" menu.
If the "Input type" in menu "Signal Input" is set to Input A or direction detection, the
switching output can be assigned only to the input A. The "Input type" setting to "dual
independent" provides both inputs A and B as the source and the selection "A + B" or
"A-B" allows the assignment of switching output both to the partial volume counters A
and B as well as the sum or subtraction.
If the "Input type" in "Signal Input" menu is changed during operation, the switching
output is automatically assigned to channel A. It is therefore recommended to check
and adjust the source of switching output in menu manually after the "Input type" is
changed.
10.7.3
Switching Output / Output 1+2 / Output type
Parameter "Output" defines the function of the transistor output. NPN, PNP or PP
(Push-pull) output types are available. The push-pull type combines NPN and PNP
and is therefore the best choice for most wiring. All outputs are equipped with short
circuit and overload protection.
10.7.4
Switching Output / Output 1+2 / Switching function
The "Function" specifies the mode of action of the outputs. In the default setting
"normally open", the output is active (connected) if the measured value exceeds the
threshold. This feature is also known as "open function", "circuit principle" or "N/O"
(normally open).
When setted to "normal closed", the output below the switching threshold is already
active and is deactivated when the measured value exceeds the threshold. This
feature is also known as "normally closed", closed-circuit principle "or" N/C "(normally
close).
10.7.5
Switching output / Output 1+2 / Switching threshold
Switching threshold is a limit value function and a upper window point for window
function..
Summary of Contents for ZOK-ExK
Page 19: ...ZOK E Z ZOK K14 0917 Page 19 Wiring for ZOK Zx with Supply option 0 and 6 ...
Page 20: ...ZOK E Z Page 20 ZOK K14 0917 7 5 8 DOR with voltage pulse output DOR with Hall sensor output ...
Page 32: ...ZOK E Z Page 32 ZOK K14 0917 8 2 4 Display layout in measuring mode for dossier ZOK Z2 ...
Page 57: ...ZOK E Z ZOK K14 0917 Page 57 ...
Page 59: ...ZOK E Z ZOK K14 0917 Page 59 13 Dimensions ZOK ZxK ZOK Ex Zx ZOK ZxP ZOK ZxF ...