7.7.3
3-Wire Configuration as passive output, current sink
(only ZOK-Z3 with Supply option ‘3/6’)
In the wiring 3-wire passive current sink, the load (load) is connected between current
output (+) and voltage source (+Vs). In the 3-conductor wiring, all types of sensors can
be connected and all other outputs can be used. If the electronic is connected in 3-
conductor wiring, the display will show „EXT“ at top left (external power supply). The
wiring type must be set to "3-WIRE" in the Analogue Output menu. All sensor types
can be connected at the signal input.