NUS-4
NUS-4 K05/0216
Seite 15
8.3.5 QUICKSET
Recommended as a simple and fast way to start up NUS-4.
QUICKSET programming (aided by 6 screens) is used in
uncomplicated level metering applications to set the 6 basic
parameters. The other parameters can only be modified in the
Full Parameter Access Mode see 9.1 (P01).
Engineering unit for the display (Metric or US)
Maximum measuring distance (H)
Assignment of min level to 4 mA
Assignment of max level to 20 mA
Error indication by the current output
Damping
time
QUICKSET program mode can only be used in measuring mode
Level (LEV) (see P01 in 9.1 Measurement Configuration)
Keys
Function
ENTER
E
+ DOWN (press for
min 3 secs!)
Enter or exit QUICKSET programming mode
UP , DOWN , NEXT
Increase/decrease and move left the blinking digit
UP + DOWN
“GET LEVEL" - display actual level measured by the NUS-4
ENTER
E
Save readout and step to the next screen
NEXT + UP
Quit Current Output Scaling without saving the modifications
(CANCEL)
NEXT + DOWN
Display of the DEFAULT value.