Page 66 of 118
OPERATING MANUAL TMU-W / UMC4
DENSITY functional class
The functional class DENSITY is comprised of the functions that affect the lower- and the upper-range value
and the processing of the measured density values. The additional service functions regarding density
calibration will not be described in these instructions.
DENSITY
Density
measurement
on/off
Density unit
DENSITY
functional class
Measurement
[on]
________________
on
off
fixed
Density in
[g / l]
_______________
kg / l
g / l
g / cm³
lbs / ft³
lbs / USG
kg/m³
lb/USB
xxx
Density
lower range val
Density 0 % =
0600 g/l
Density
upper range val
Density 100 % =
1100 g/l
Density
limit MIN
Density
MIN = 0979.0 g/l
Density
limit MAX
Density
MAX = 1200.0 g/l
Density limit
hysteresis
Density limit
Hyst.= 000.5 g/l
Density limit
for empty pipe
Pipe emty below
0500 g/l
Display ref./
Process dens.
Calibr. density
hot medium
Measured. Values
hot medium
Finish calibration
of density
Display of
[Process density]
________________
Reference density
Process density
Frequency / temp.
measure [no]
_________________
yes
no
060.50°C 166.409 Hz
Rho= 0994.1 g/l
Calculate?
[no]
______________
yes
no
Fixed density
setting
Fixed density
0998.1 g/l
Ref.-density
Temp. coeff.
Ref.-density
Ref. temperature
Ref.-density
operat. pressure
Temp.coeff.
+00.000 E-5/K
Ref. temperature
015.00 °C
operat. pressure
001.000 bar
Factor density
progr. unit
F =0998 g/l