Adjust the knob to " " when the ambient light level matches with the
desired value (See FIG.10-A).
When the knob is set to " " originally, it should be adjusted to other
position more than 1sec, then goes back to " " (See FIG.10-B).
Then the load is off. red LED starts to flash slowly indicating entering into
learning mode. Learning will be completed within 25 seconds. Afterwards,
the red LED and load will keep on 5sec or red LED flashes quickly for 5sec
and load is off to confirm successful learning (See FIG.10-C).
After learning procedure, the detector returns to AUTO mode with red
LED and load being off.
KDP-DALI 01
Presence detector for DALi lighting control
37
Instructions manual |
www.grupotemper.com
Operation and function
Time, Lux, STBY and STBY% knobs
Lux learning function with knob
Learning procedure:
Knob
Function
Knob setting
Time
10m.
30m.
5m.
1m.
60m.
Test
Lux
5
300
100
2000
Set load on time in
standby mode
3 precise adjustments: 5min,
10min, 15min, plus ∞.
Set load illumination
in standby mode
•
•
•
•
3 precise adjustments: 10%, 20%,
30% and OFF (Load is off in
standby mode)
10%
OFF
20%
30%
STBY%
STBY
15m
10m
5m
∞
Set delay off time for
load lighting
Range : Approx. 1min to 60min
Test : Test mode (Load and red
LED will be 2sec on, 2sec
off)
Set the light value for
switching on load
lighting
Range :Adjustable from
approx.5 to 2000Lux.
(learn): The actual ambient
light level
(10 - 2000Lux) can be
read in.