ETS Parameter
Setting
{Factory Default}
Comment
Behaviour on alarm
activation
disabled;
send value 0; send value 1; set
value to 0; set value to 1
{
send value 1
}
Select action on entering the threshold range
Behaviour on alarm
deactivation
disabled;
send value 0; send value 1; set
value to 0; set value to 1
{
send value 0
}
Select action on leaving the threshold
(+hysteresis) range
Device temperature
Device temperature [°C]
disable; enable
{
disable
}
Enable/disable group associations, measurement
and following settings
Sending difference
2°C; 3°C; …10°C
{
2°C
}
Difference between actual and last sent value
which triggers the sending
Cyclic sending
disabled;
1min; 2min…5min; 10min;
15min…30min; 1h; 2h…8h
{
disabled
}
Info telegram is sent regularly
Alarm settings
disable; enable
{
disable
}
Enable/disable the alarm function
Threshold
0…110[°C]
{
70
}
Select threshold value to execute the
«
Behaviour
on alarm activation
»
Hysteresis
1…40[°C]
{1}
Select hysteresis interval value to execute the
«
Behaviour on alarm deactivation
»
Behaviour on alarm
activation
disabled;
send value 0; send value 1; set
value to 0; set value to 1
{
send value 1
}
Select action on entering the threshold range
Behaviour on alarm
deactivation
disabled;
send value 0; send value 1; set
value to 0; set value to 1
{
send value 0
}
Select action on leaving the threshold
(+hysteresis) range
Table 5.
Measurements tab parameter settings
Using the
«
Sending difference
»
function with the
«
Output voltage
»
is possible only within the
«
Alarm 1,2,3,4
"
tabs like described in chapter
3.7
.
The «Output voltage» value is valid only if most of the loads is on the KNX bus output
If the
«
Output current
»
value is < 10 mA, for calculations, the input voltage is assumed to be at 230 V
AC