2.4.2  INDIVIDUAL ADDRESS ASSIGNMENT

To configure the device an interface connection (IP, USB) to the KNX bus system is required. The device is 
supplied with the Individual Address 12.12.255. The KNX product database entry (available for ETS4 and 
higher) can be downloaded from the website and from the KNX Online Catalog.

With the ETS the Individual Address can be assigned to the device by setting the desired address in the 
properties  window  of  the  ETS.  A er  starting  the  ETS  download  and  then  pressing  the  Programming 
Button the device restarts itself.

Figure 1.

 ETS properties window

page 10

module-electronic.ru

Summary of Contents for Module PS-S.640.30.1

Page 1: ...module electronic ru KNX POWER SUPPLY PS S 640 30 1 Application Program ver 1 0 User Manual ver 1 0 User Manual...

Page 2: ...ter reset 8 2 3 Parameter structure for measurement sources 9 2 4 Programming 9 2 4 1 Programing button 9 2 4 2 Individual address assignment 10 2 5 KNX bus reset function 11 3 ETS database parameters...

Page 3: ...in the KNX bus and protective against short circuit and overload Compact housing 2TE Additional output 29V DC Diagnostic function LED status indication Output current 640mA Leakage 5W Mains voltage 23...

Page 4: ...x current total output 640mA 1 2A E iciency at nominal load 82 KNX interface Speci cation TP 256 Available application so ware ETS 4 and later KNX connector 4 wire EIB connector PUSH WIRE spring clips...

Page 5: ...ge is 195 265V AC Red Input voltage is out of this range 2 Bus voltage VBUS Green KNX bus voltage 28 31V DC Red KNX bus voltage is out of this range 3 Telegram tra ic Green blinking Telegram tra ic 80...

Page 6: ...y be carried out by quali ed personnel There is a risk of electric shock Be sure to turn o the power before installing or removing the device Even when the device is turned o the output terminals can...

Page 7: ...a tracking period can be set At the end of every tracking period the maximum measured value can be sent on the bus or just be set as value of the appropriate object Four di erent Alarm tabs see chapt...

Page 8: ...Counter Duration Counter Overload X X Short Circuit X Load Detached X KNX Bus Reset X Threshold Range X X Operating Time total since last startup X Device Startup X Table 1 Available event counters 2...

Page 9: ...lic sending The actual value is periodically sent Threshold alarm Enables disables the threshold functionality and following options Threshold Crossing this limiting value executes the Behaviour on al...

Page 10: ...atabase entry available for ETS4 and higher can be downloaded from the website and from the KNX Online Catalog With the ETS the Individual Address can be assigned to the device by setting the desired...

Page 11: ...KNX Bus Reset is triggered a er a reset by button press and a er a reset by communication object A Device Startup takes place when there was a mains power outage or a er programming the device The nu...

Page 12: ...ent and the temperature measurement can be activated The Maximum tracking tab contains the parameters for maximum current value and maximum temperature value detection within a Tracking Period In the...

Page 13: ...tion during the time delay no telegrams are sent Then the Power supply is on telegram is the rst one that is sent Figure 3 General tab parameters ETS Parameter Setting Factory Default Comment Heartbea...

Page 14: ...ed and located outside the working range 28 31V For example with no Output voltage hysteresis the Behaviour on alarm deactivation function is executed on just entering the working range The Output cur...

Page 15: ...1 set value to 0 set value to 1 send value 0 Entering the working range Output current Output current mA disable enable disable Enable disable group associations measurement and following settings Obj...

Page 16: ...able Enable disable the alarm function Threshold 0 110 C 70 Select threshold value to execute the Behaviour on alarm activation Hysteresis 1 40 C 1 Select hysteresis interval value to execute the Beha...

Page 17: ...enable disable Enable disable group associations measurement and following settings Object type 2 byte DPT7 integer 2 byte DPT9 oat 4 byte DPT14 4 byte DPT14 Select datapoint type Automatic sending d...

Page 18: ...erence 0 100 10 Di erence between actual and last sent value which triggers the sending Cyclic sending disabled 1min 2min 5min 10min 15min 30min 1h 2h 8h disabled Info telegram is sent regularly Alar...

Page 19: ...t Behaviour on alarm deactivation disabled send value 0 send value 1 set value to 0 set value to 1 send value 0 Select action on leaving the threshold hysteresis range Table 7 Telegram tra ic tab para...

Page 20: ...ror counters can be set to zero by writing a 1 to the communication object no 33 Counter reset Figure 9 Error counter tab parameters ETS Parameter Setting Factory Default Comment Overload number count...

Page 21: ...r of short circuits disable enable disable Enable disable group associations number counter and following setting Sending di erence 0 500 0 disabled Di erence between actual and last sent value which...

Page 22: ...ontaining the actual time counter value can be sent according to the pre set value di erence The operational counters can be set to zero by writing a 1 to the communication object no 33 Counter reset...

Page 23: ...iations measurement and following setting Sending di erence 0 2 600 000 s 0 disabled 1 month 2 600 000s 1 day 86 000s Di erence between actual and last sent value which triggers the sending Operating...

Page 24: ...ion 1 Duration 2 Duration 3 Duration 4 objects no 21 24 27 30 Figure 11 Alarm 1 tab parameters same applies to alarm 2 3 4 ETS Parameter Setting Factory Default Comment Alarm 1 disable enable disable...

Page 25: ...sis range Duration 1 Sending di erence 0 2 600 000 s 0 disabled 1 month 2 600 000s 1 day 86 000s Info telegram is sent regularly when the time counter of threshold exceedance s reaches the pre set val...

Page 26: ...and passing hysteresis a telegram with value 0 or 1 is sent 1 bit X X X 4 Output current maximum Send measured value A er the expired tracking period with Automatic sending the device sends the measur...

Page 27: ...detachments due to short circuit device startup and KNX bus reset 4 bytes X X X 16 KNX bus reset Initialize Triggered by a telegram with value 0 or 1 the device starts a reset process 1 bit X X X X 1...

Page 28: ...n s indicating the number of threshold events for output current output voltage temperature 2 bytes X X X 26 Threshold 2 Send alarm status With the measured value entering the threshold range a telegr...

Page 29: ...ounter values and duration counter values except total operating time and device startup number are set to zero by a telegram with 1 1 bit X X X 34 Measured values Send all Measured values of output c...

Page 30: ...5 STATE OF DELIVERY 5 1 DEFAULT FACTORY SETTING General Individual address 12 12 255 Heartbeat 60 s page 30 module electronic ru...

Reviews: