TIME SETTINGS
Time settings will need to be done by authorized personnel only. The time settings for detergent pump, fresh water fill,
sanitizer pump, and rinse pump are done inside the control box using the single turn pots. The pots control the time dura-
tion of each of the listed components. Use the chart below to make settings.
POT
CONTROL
ACTIVE TIME
IN 90 SECONDS
SPAN OF POT
TIME
ADJUSTMENT
COMMENTS
Detergent Pump
at time = 3 seconds
2-30 seconds
pot turns from 7 o'clock to 5 o'clock or 10 divi-
sion. Each division is 2.7 seconds. Pump flow is
approximately 1.3 ml/sec.
Sani Pump
at time = 70 seconds
0-15 seconds
pot turns 7 o'clock to 5 o'clock or 10 divisions.
Each division is 1.5 seconds. Pump flow is ap-
proximately 1.3 ml/sec.
Rinse Pump
at time = 70 seconds
0-15 seconds
pot turns 7 o'clock to 5 o'clock or 10 divisions.
Each division is 1.5 seconds. Pump flow is ap-
proximately 1.3 ml/sec.
Fill Start
at time = 48 to 59
seconds
0-11 seconds
fill start is activated during the fixed drain cycle
(45 to 60 seconds) at the 7 o'clock setting time
is 0 and will start fill at 48 seconds in cycle. At
the 5 o'clock setting time is 11 seconds and will
start fill at 59 seconds in cycle. Fill start is set
according to water pressure and the required
time to rinse debris down the drain. Normal
setting at 20 psi flow pressure is 12 o'clock or
5.5 seconds.
Fill Time
determined by fill start
10-42 seconds
begins at the setting of the fill start. Once fill
start is set the fill time determines the duration
of time fresh water solenoid valve remains open.
7 o'clock setting time is 10 seconds, 5 o'clock
setting time is 42 seconds. Adjust according to
water pressure. Normal setting at 20 psi flow
pressure is 11 o'clock or 15 seconds.
sanitizer pump pot.
rinse pump pot.
Fill time pot.
Fill start pot.
Page No. 3
(11/10/01) Revision F, EO 4109 Part No. 9641606
Det. Pump pot.
Fuse 1 Amp 250V
Fuse 1 Amp 250V
Fuse 3 Amp 250V
Fuse 2 Amp 250V