16
It is required that near boiler piping
systems utilize the
Primary/Secondary
configuration shown in FIG. 3-10 only.
The use of other near boiler piping
configurations could result in improper
building and system flow rates leading to
inadvertent boiler high limit shutdowns
and poor system performance.
NOTICE
Pump sizing and flow requirements are
based on 20 feet of piping, 4 - 90°
elbows, and 2 - fully ported ball valves.
NOTICE
3
Hydronic piping
Variable speed pump option
Table 3B Recommended Variable Speed Pumps
*The minimum temperature rise is derived from the chart in FIG. 3-3 with the firing rate and pump speed at 100% as shown in
the table above.
The shaded regions of pump coverage are only available for applications with 230V (60 Hz) supply voltage, all others are
to be 115V. (A field supplied relay is required to connect the 230V pump listed in the shaded area in Table 3B to the boiler
high voltage terminal strip.)
Variable speed pump setup
Before operation, ensure the following:
- Pump is set for an input signal of 0 - 10Vdc by the dip switches on the pump control
- Pump is set for external signal control (if applicable)
- Pump is set for linear output (if applicable)
- If pump does not come equipped with a 0 - 10 Vdc input option, an optional module
will be required from the vendor
Minimum Temperature Rise*
Model
Pump
Grundfos
UP26-96 FC/VS
TACO
0013 IFC VS
Wilo
Stratos 1.25 3 x 30
151
21
20
19
211
27
25
24
286
27
24
22
SMART SYSTEM / Multi-temperature loop
control option
The outdoor boiler is capable of producing up to three (3) set
point temperatures to meet different space heating demands.
When using more than one temperature demand it is necessary
to protect the lower temperature loop from overheating. To
help aid with this protection, Lochinvar offers the Multi-
Temperature Loop Control Board Kit (RLY30086).
Outdoor Knight Boiler Installation & Operation Manual