151
211
286
Flow Rate (GPM)
Pressure Drop vs. Flow (Includes Secondary Piping)
Pressure Drop (Feet of Head)
Figure 3-3 Pressure Drop vs. Flow
20°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
151
14
20
1"
UPS26-99F
0011
NRF-36
E7
211
20
29
1"
UPS32-160
1400-50
PL-55
E9*
286
27
15
1-1/4"
UPS32-80
1400-20
PL-36
E11
Table 3A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°
25°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
151
11
13
1"
UPS26-99F
0014
NRF-36
E7
211
16
19
1"
UPS26-99F
0013
NRF-36
E7
286
21
12
1-1/4"
UPS26-99F
0011
NRF-36
E7
Pumps listed in bold type are provided by the factory as the boiler circulation pump on standard altitude
models.
NOTICE
35°F Temperature Rise Applications
Model
GPM
FT/HD
Minimum Pipe
Size
Pump
Grundfos
TACO
B & G
Armstrong
151
8
10
1"
UPS15-58FC
008/0010
NRF-36
Astro-30
211
11
9
1"
UPS15-58FC
0010
NRF-36
Astro-50
286
15
7
1-1/4"
UP26-64F
008/0010
NRF-36
E7
Pumps listed in italicized type are provided by the factory as the boiler circulation pump on high altitude
models.
NOTICE
The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation.
NOTICE
3
Hydronic piping
(continued)
These pumps are only slightly above 20° rise flows, but are the closest available. To reach a 20° rise or less, an
upsized pump will be required.
*NOTICE
Outdoor Knight Boiler Installation & Operation Manual