3
Troubleshooting
48
Table 3-4
(continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Boiler Interface
FAULT
DESCRIPTION
CORRECTIVE ACTION
Low 24 vac
120 vac input to the main control board has
dropped below 80 vac.
• Check 120 vac supply to the transformer.
• Check wiring connections at the low voltage terminal
strip.
• Check the wire size/length to remote devices.
• Replace the transformer.
Watch Dog Error
The main control board has detected an
internal fault.
• Cycle power to the boiler.
• Replace the main control board.
Write EEProm
The main control board has detected an
internal fault.
• Cycle power to the boiler.
• Replace the main control board.
CRC Parameters
The main control board has detected an
internal fault.
• Cycle power to the boiler.
• Replace the main control board.
No Error Stored
The particular lockout information has been
lost.
• Press the RESET button.
• Replace the main control board.
Service Manual