BMS Thermostat Input
When controlling the boiler through the 0 - 10V BMS input,
BACnet, or ModBus, the boiler can be enabled one of two
ways. With the
BMS Thermostat Input parameter
set to
ACTIVE, the boiler will be enabled by closing the Heat/
Loop Demand 1 input. When set to INACTIVE, the boiler
will be enabled by the voltage level on the 0 - 10V input (in
the case of 0 - 10V BMS control), or the 0 - 10V input value
received through BACnet or ModBus. The default value is
INACTIVE.
On Volts
When programmed for BMS control through the 0 -
10V BMS input or through ModBus/BACnet and the
BMS Thermostat Input is set to INACTIVE, the
On Volts
parameter determines the 0 - 10V BMS input voltage at
which the boiler is enabled. The minimum value is 0.5V and
the maximum is 10.0V. The default value is 2.0V.
Off Differential Volts
When programmed for BMS control through the 0 - 10V
BMS input or through ModBus/BACnet and the BMS
Thermostat Input is set to INACTIVE, the
Off Differential
Volts
parameter determines how far below the
On Volts
setting the 0 - 10V BMS input voltage must be in order
to disable the boiler. The minimum value is 0.2V and the
maximum is the
On Volts
setting. The default value is 1.0V.
ModBus/BACnet
When BMS is set to ACTIVE (see BMS Active / Inactive) and
the boiler is being controlled through BACnet or ModBus,
set
ModBus/BACnet
parameter to ACTIVE. Otherwise, set
the
ModBus/BACnet
parameter to INACTIVE. Note that
the boiler can still be monitored by ModBus or BACnet
with this parameter set to INACTIVE. The default value is
INACTIVE.
BAS T/O
This is the amount of time the unit controls will wait to
receive a communication string from the BMS controller
before reverting back to its own internal parameters. This
parameter is adjustable by the installer by accessing the
BAS
T/O
parameter
.
The adjustment range of this parameter is 5
seconds to 2 minutes.
The default value is 10 seconds.
1
Service
Rate at Minimum Volts
When programmed for BMS control through the 0 - 10V
BMS input or through ModBus/BACnet and the BMS Type
is programmed as POWER, the modulation percentage
represented by the
Volts at Minimum
parameter is set by the
Rate at Minimum Volts
parameter. The minimum value is 0%
and the maximum is the
Rate at Maximum Volts
setting. The
default value is model dependant.
Rate at Maximum Volts
When programmed for BMS control through the 0 - 10V
BMS input or through ModBus/BACnet and the BMS Type
is programmed as POWER, the modulation percentage
represented by the
Volts at Maximum
parameter is set by the
Rate at Maximum Volts
parameter. The minimum value is the
Rate at Minimum Volts
setting and the maximum is 100%. The
default value is 100%.
Set Point at Minimum Volts
When programmed for BMS control through the 0 - 10V
BMS input or through ModBus/BACnet and the BMS Type
is programmed as SETPOINT, the set point represented by
the
Volts at Minimum
parameter is set by the
Set Point at
Minimum Volts
parameter. The minimum value is 32°F (0°C)
and the maximum is the
Set Point at Maximum Volts
setting.
The default value is 70°F (21°C).
Set Point at Maximum Volts
When programmed for BMS control through the 0 - 10V
BMS input or through ModBus/BACnet and the BMS Type
is programmed as SETPOINT, the set point represented by
the
Volts at Maximum
parameter is set by the
Set Point at
Maximum Volts
parameter. The minimum value is the
Set
Point at Minimum Volts
setting and the maximum is 190°F
(88°C). The default value is 180°F (82°C).
Volts at Minimum
When programmed for BMS control through the 0 - 10V BMS
input or through ModBus/BACnet, the
Volts at Minimum
parameter should be set to the minimum voltage signal sent
to the SMART SYSTEM control. The range of this parameter
is 0.0V to the
Volts at Maximum
value. The default setting is
2.0V.
Volts at Maximum
When programmed for BMS control through the 0 - 10V BMS
input or through ModBus/BACnet, the
Volts at Maximum
parameter should be set to the maximum voltage signal sent
to the SMART SYSTEM control. The range of this parameter
is the
Volts at Minimum
value to 10.0V. The default value is
10.0V.
28
Service Manual