Input Data for Strain Gauge (DMS)
Input
-7.5 mV/V ... 7.5 mV/V
Bridge resistance
200 Ω ... 10 kΩ
Zero adjustment
within the input range
Supply current (int. supply)
0 ... 5 mA
Supply voltage
(external supply)
for T ≤ 55 °C: 1 ... 3 V
for T > 55 °C: 1 ... 2.8 V
Line monitoring
for short circuits or open circuits
Accuracy
± (2 μV/V + 0.1 % meas.val.)
for spans ≥ 0.5 mV/V
Temperature coeffi
cient at
input
50 ppm/K of adjusted sensitivity
(average TC in permitted operating
temp range, reference temp 23 °C)
Overload capacity
5 V across all inputs