55
Configuration using Switches: Example
Sensor:
Thermocouple type J
Measuring range:
200 ... 1200 °C
Output signal:
4 ... 20 mA
1. Adjust sensor type:
TC Type J:
DIP1 = 1, DIP2 = 0, DIP 3 = 0
2. Adjust start value:
200 °C
This start value is composed of: numerical value = 20, factor = x10.
Adjust numerical value using rotary switches:
20
Adjust factor x10:
DIP4 = 0, DIP5 = 1
3. Adjust end value:
1200 °C
For end values above 1000 °C, adjust factor x10 + 1000
Adjust numerical value using rotary switches:
20
Adjust factor x10 + 1000:
DIP6 = 1
4. Adjust output signal:
4 ... 20 mA:
DIP7 = 0, DIP8 = 1
Note
Cover the switches with the included
self-adhesive polyimide tape after
completion of confi guration.
Summary of Contents for PolyTrans P 32000 P0 Series
Page 18: ...18 Konfigurierung über Schalter Funktionsübersicht DIP Schalter ON ...
Page 20: ...20 ...
Page 34: ......
Page 35: ......
Page 37: ...The Art of Measuring www knick de PolyTrans P 32000 P0 English 37 Universal Transmitters ...
Page 54: ...54 Configuration using Switches Overview of Functions DIP switch ON ...
Page 56: ...56 ...
Page 70: ......
Page 71: ......
Page 73: ...The Art of Measuring www knick de PolyTrans P 32000 P0 Français 73 Convertisseurs universels ...
Page 90: ...90 Configuration via les commutateurs Aperçu des fonctions Commutateur DIP ON ...
Page 92: ...92 ...
Page 106: ......
Page 107: ......
Page 109: ...The Art of Measuring www knick de PolyTrans P 32000 P0 Português 109 Transmissores Universais ...
Page 126: ...126 Configuração Usando Chaves Sinopse de Funções Chaves DIP ligadas ON ...
Page 128: ...128 ...
Page 142: ......
Page 143: ......