FlexStat
20
Operation Guide, Rev. L
See the FlexStat Application Guide for more infor-
mation about custom programming for Hospitality
mode.
NOTE: If this new feature does not work (is
“Inactive”) after upgrading the firmware
(especially from R1.3.0.4 or earlier), you
may need to restore the factory default
(especially if there is custom programming
or configuration in the FlexStat) and
reconfigure the FlexStat. See
Restore
Factory on page 25
.
NOTE: Auto in System Mode does not currently
have an icon implemented with it.
Manually selecting Heat or Cool will
display an icon on the Home screen.
Rotation Values
ROTATION VALUES
1:
2: OAT: HIDE
3: CO2: SHOW
4: UI4: HIDE
HUM: SHOW
The Rotation Values menu allows easy setting of
what applicable optional values (e.g., humidity,
outside air temperature, and/or CO
2
level) will
display on the lower right of the screen (such as
“HUM: 46% RH” shown on the Hospitality Mode
sample screen).
In applicable models, humidity and CO
2
levels are
shown by default but can be hidden if desired.
If more than one value is shown, the values will
rotate approximately every five seconds.
UI4, the fourth rotation value, is available for custom
programming (using BACstage or TotalControl).
To program UI4 to display setpoint, MAT, or other
value, see the Sample Custom Applications section in
the FlexStat Application Guide.
Show Temperature Tenths (Decimals)
With R2.0.0.13 and later firmware, Fahrenheit tem-
perature values on the display change in whole
degree increments by default, and Celsius values
change in 0.5° increments. Changing the default
No
to
Yes
will show tenths of a degree values for both
scales.
This does not affect setpoint adjustments, which are
always in whole degree increments for Fahrenheit
and half degree increments for Celsius.
For Hospitality mode, Setpoint Control configuration
options are Single Setpoint or Schedule:
•
Single Setpoint
will keep the setpoint at what-
ever the user has last selected (except when a
motion sensor optionally puts the FlexStat in
standby mode—see
Motion Sensor Setup on page
8
). The FlexStat will stay On (in occupied mode),
and the schedule will be ignored.
• To use the
Schedule
option, the schedule must
be configured
before
entering Hospitality mode.
(See
Schedules on page 22
.) If no schedule is config-
ured by the user, the default schedule is always
On (occupied).
Pushing
Left
Button
Goes to Field A Screen
(Field A Selection)
(Field B Selection)
(
Field C Message
)
(Pushing
Right
Button
Goes to
Field B
Screen)
(No Field C Screen Exists)
WED 10/01
3:20 PM
COOL
HIGH
WELCOME
HUM: 46% RH
SYSTEM MODE
AUTO
HEAT
COOL
OFF
–>
(Hospitality Mode Sample Screens)
Pushing
Enter
Button Toggles
°F/°C Temperature Scale
(Rotation Value)
Custom Hospitality mode programming is required
for:
• Use of
Field C
for displaying messages.
• Creating additional/alternate menu options.
• Any use of AHU or RTU applications in firm-
ware
R1.3.0.11
. (Firmware earlier than R1.3.0.11
did not support Hospitality mode at all, and
R1.3.0.11 natively supported only FCU or HPU
applications in Hospitality mode. The latest firm-
ware supports all the applications.)