FlexStat
10
Operation Guide, Rev. L
(Advanced) CB (Control Basic) Programs
CB PROGRAMS
PROG1:
PROG2: RUNNING
PROG3: RUNNING
PROG4: RUNNING
PROG5: RUNNING
PROG6: HALTED
PROG7: IDLE
RUNNING
PROGRAM #1
SETPOINTS & MODES
AUTO-RUN: TRUE
CHANGE: READY
STATE: RUNNING
HALT REASON: NORMAL
HALT DESC:
OUT OF SERVICE: FALSE
To halt or load/run the built-in (1–5) and custom
(6–10) Control Basic programs, press:
1. Up
/
Down
to move among entries.
2. Enter
to select.
3. Right
/
Left
to move among value fields.
4. Up
/
Down
to increment/decrement value.
If
custom
Control Basic programs are installed and
a
restore to factory settings is performed, all factory
programs are restarted but all custom Control Basic
programs are halted.
Change the state of each pro-
gram by loading/running the program from the CB
Programs menu (or BACstage or TotalControl).
If
custom
Control Basic programs are installed
and
set to autorun
, whenever the
firmware is updated
,
ALL (factory and custom) programs are halted.
If
custom
Control Basic programs are installed
but
NOT set to autorun,
whenever the firmware is up-
dated, factory programs are restarted but any (manu-
al) running
custom
programs are
halted
at restart.
Change the state of each custom program by using
the Update Manager or loading/running each pro-
gram from the CB Programs menu (or BACstage or
TotalControl).
UPDATE MANAGER
PROGRAM CONFIG ERROR
ENABLE FACTORY:
ENABLE CUSTOM: NO
EDIT CB PROGRAMS
DONE
NO
In the About menu, ASV will show CUSTOM if any
built-in Control Basic program (1–5) is not running
or has auto-run disabled. See
About the FlexStat on
page 6
.
NOTE:
Customized programs are the responsibility
of the user.
KMC Controls does not provide
support for such programs.
(Advanced) CO
2
Sensor (and DCV)
CO2 SENSOR
SENSOR INFO
CALIBRATION
CO2 SENSOR INFO
MODEL: T6615
SUB VOL: A15
SW DATE: 090217
S/N: AB00011759
CO2: 873
ELEVATION: 0
STATUS: NORMAL
CO2 CALIBRATION
ELEVATION: 0
REFERENCE GAS: 300
MODE: MONITOR
CO2: 1067
STATUS: NORMAL
CAL TIME: 00:00
CO
2
Sensor Setup and Information
NOTE: Set the desired CO
2
setpoint under the
Setpoints menu. See
Setpoints on page 23
.
To view information about the sensor, set the eleva-
tion, and (depending on model) calibrate the sensor,
press:
1. Up
/
Down
to move among CO
2
Sensor Info
entries.
2. Enter
to select.
3. Right
/
Left
to move among value fields.
4. Up
/
Down
to increment/decrement value.
For maximum sensor accuracy,
enter the elevation
(altitude) above sea level
of the building’s location.
(The default value is 0.) Elevation for any particular
location can be found at such sources as
www.earth-
tools.org
. (For very tall buildings, the upper floors
would have a higher elevation than lower floors.)
After power is first applied or the FlexStat is restart-
ed, the sensor goes through a
warm-up
for approxi-
mately half a minute. During the time the sensor
count will be 0 ppm and the Status line will display
WARMUP instead of NORMAL.
The
sensor and its firmware
are identified by the
model, the compilation subvolume (SUB VOL), com-
pilation date (SW DATE in yymmdd format), and
serial number.
NOTE: With the CO
2
sensor enabled, a trend log is
automatically generated. See
(Advanced)
Trend Logs on page 19
.