FlexStat
16
Operation Guide, Rev. L
(Advanced) BACnet Device Properties
DEVICE
INSTANCE:
NAME: FlexStat_101
LOCATION: KMC Controls
1
To set the BACnet device instance, name, and
location, press:
1. Up
/
Down
to move among entries.
2. Enter
to select.
NOTE: In firmware versions R1.3.0.4 and earlier,
the FlexStat could also be restarted or
restored to factory defaults from this
menu.
In R2.0.x, this function was moved to
a separate menu. See
(Advanced) Restart/
Restore on page 17
and
Resetting the FlexStat
on page 24
for more information about that
function.
(Advanced) Inputs
INPUTS
1: SPACE TEMP
2:
3: MIXED AIR TEMP
4: OUTSIDE AIR TEMP
5: SPACE HUMIDITY
7: REMOTE SPACE TEMP
8: AI_08
DISCH AIR TEMP
INPUT #2
DISCH AIR TEMP
VALUE: 60.0° F
CAL. OFFSET: 0.0
OUT-OF-SERVICE: FALSE
SENSOR:
10K TYPE III
Inputs vary according to model, selected application,
and selected application options. See
(Advanced) Ap-
plication and Additional Setup on page 7
.
To change sensor type and calibration offset, press:
1. Up
/
Down
to move among entries.
2. Enter
to select.
3. Right
/
Left
to move among value fields.
4. Up
/
Down
to increment/decrement value.
Value will show a temperature reading or a voltage
(0.0 to 3.0), depending on the sensor. Analog sensors
can be calibrated using the Calibration Offset option.
(Advanced) Temp. Setpoint Limits
LIMITS
OCC MIN CLG:
OCC MAX HTG: 80° F
UNOCC MIN CLG: 66° F
UNOCC MAX HTG: 80° F
MIN SETPT DIFF: 2° F
66° F
To set the minimum and maximum allowed user/
operator setpoint values, press:
1. Up
/
Down
to move among entries.
2. Enter
to select.
3. Right
/
Left
to move among value fields.
4. Up
/
Down
to increment/decrement value.
NOTE: For Minimum Setpoint Differential, see the
diagram.