FlexStat
14
Operation Guide, Rev. L
if it is not already at that position. See
DCV
(Demand Control Ventilation) on page 21
.
VENT OVRIDE (MINS)
= Amount of time for
Ventilation Override operation (30 minutes
default). See
DCV (Demand Control
Ventilation) on page 21
.
(Advanced) Communications (BACnet)
COMMUNICATIONS
ACTIVE:
ETHERNET SETTINGS
IP SETTINGS
FOREIGN DEV SETTINGS
MS/TP SETTINGS
CONFIGURE
COMMUNICATIONS
ACTIVE:
MAC: 00:D0:6F:89:00:01
ETHERNET
COMMUNICATIONS
ACTIVE:
IP ADDRESS: 192.168.1.254
SUBNET MASK: 255.255.0.0
GATEWAY: 255.255.255.255
UDP PORT: 47808
IP
COMMUNICATIONS
ACTIVE:
IP ADDRESS: 172.16.1.254
UDP PORT: 47808
TIME TO LIVE (SECS): 600
FOREIGN DEVICE
COMMUNICATIONS
ACTIVE:
MAC ADDRESS: 1
BAUD RATE: 38400
AUTO-BAUD: OFF
MAX MASTER: 127
MS/TP
For MS/TP communications, connect the EIA-485
wiring to
–A
and
+B
terminals on the backplate (see
the relevant model’s installation guide). For Ethernet
IP, and Foreign Device communications (on relevant
“E” models), plug an Ethernet cable directly into the
RJ-45 modular jack on the back of the FlexStat.
To set protocol and parameters for BACnet
communications,
select Configure
, and then press:
1. Up/Down
to move among entries.
2. Enter
to select.
3. Right
/
Left
to move among value fields.
4. Restart the FlexStat for the new protocol to
become Active. (See the Device menu.)
NOTE: Even if MS/TP is the only option in
firmware R2.0.0.6 and later,
Configure must
first be selected before any of the values
can be changed
. Otherwise the values are
read only.
Only one protocol can be enabled at any time. The
IP/Ethernet modes do not serve as routers for the
MS/TP connection.
For
MS/TP
EIA-485 communications, the Max
Master is the highest MAC address a device will
attempt to locate when polling for master devices on
the local network. To avoid possible communication
issues with the network or a computer connected
through a KMD-5576 USB Communicator,
the Max
Master number should be the lowest number
needed for that network. To communicate with a
KMD-5576 through the data port at the bottom of
the case, IP/Ethernet-enabled FlexStat models in
one of the Ethernet or IP modes must (temporarily)
be set for MS/TP mode (and restarted).
(See
Resetting the FlexStat on page 24
.)
For
IP
and
IP Foreign Device
communications,
consult with the system administrator for the
appropriate settings for the IP Address, Subnet
Mask, Gateway, and UDP Port.
Ethernet
communications are essentially plug-and-
play, and the MAC address is not changeable.