Operating Instruction
Healthcare chiller of the KSC Series
Version „Revision 09“
Type KSC 215-L-U/S
page 5von138
\\FILER02\Allgemein\02 - Technische Unterlagen KKT\Originale\830xxx Bedienungsanleitungen\KSC\83002302.Ka KKT chillers_KSC215-US.doc
1.4
Safety Warnings:
-Cooling water circuit is pressurized.
-Switch off the Chiller and depressurize before servicing the cooling water circuit.
-Drain water from pipes and spare parts before shipment.
-Do not operate the Chiller without ethylene glycol! The cooling water must contain min. 35% to max. 38%
ethylene glycol.
-Nominal static filling pressure when Chiller has been switched off: 1,5bar.
-Don`t handle valves while the Chiller is running
-Ethylene glycol be added at the rate of min. 35% to max. 38% of the volume of water anytime otherwise
warranty void.
-The rate depends not on the local ambient temperature.
-Don’t use automotive antifreeze.
-Voltage continuous to be present at the terminals, even after the MR system has been switched off.
-Parts in the refrigerant circuit are hot, even the Chiller has been switched off.
-WEAR SAFETY GLOVES AND GLASSES WHEN WORKING ON UNIT TO AVOID INJURY!
-WEAR LONG SLEEVE SHIRT AND PANTS WHEN WORKING ON UNIT!
-NO LOOSE CLOTHING ITEMS ALLOWED TO AVOID INJURY!
-PLEASE READ THE MANUAL!
Additional see the safety notes for refrigerant and oil page 113.
OBSERVE THE SAFETY RULES
Before commencing work on the unit, switch the plant to voltage-free
IN CASES OF EMERGENCY TURN OFF THE AGGREGATE BY THE MASTER SWITCH !
Caution!
Work on electric and refrigerant circuits should only be performed by qualified operatives
Observe the safety rules!
Warranty void if manual removed from chiller.
Do not remove the Secure Digital Memory card from the CPU before the chiller is switched off!!!!!!