Operating Instruction
Healthcare chiller of the KSC Series
Version „Revision 09“
Type KSC 215-L-U/S
page 18von138
\\FILER02\Allgemein\02 - Technische Unterlagen KKT\Originale\830xxx Bedienungsanleitungen\KSC\83002302.Ka KKT chillers_KSC215-US.doc
4
Technical Specifications
4.1
Data sheet
Model
Outdoor
Dimensions
Depth
940
mm
Breadth 3040
mm
Height 1850
mm
Weight without refrigerant load
ca.
1070
kg
Weight with load
ca.
1100
kg
Shipping weight
ca.
1600
kg
Weight total refrigerant load
24,0 kg
CO2 equivalent
34,4 t CO2
Number of fans
4
Quantity of air
2x
18000
m³/h
Refrigerant
R134a
GWP
1430
Required quantity of refrigerant
See name plate
High-pressure switch
19,2 bar
Water connection inlet
2“
G" female
Water connection outlet
2 “
G" female
Cold water temperature outlet
min.
19
°C
Cold water temperature outlet
max.
22
°C
Tolerance
±0,5 K
Primary water pump type
CR 10- 05
Rated water capacity
min.
7,8 m³/h
Rated water pressure
7,5 bar
Ambient temperature
min.
-20
°C
max.
+48
°C
Cooling capacity
60,0 kW
Rated cold water outlet temperature
20
°C
Temperature of surroundings
48
°C
Main supply
480 V / 3Ph / 60 Hz
Control voltage
24
VDC
Fluctuations in main voltage
max.
-14/+10 %
Fluctuations in Frequency
max.
±1
Hz
Power input
max.
29
kW
Loudness
at 10 m
61
db(A)