KP310V1.0 Controller Operation Manual
- 22 -
8.2.1.5 Remote start & stop normally open
In the “Remote mode ”,After Terminal “8” is closed
(
low potential
)
,genset start after remote
start delay
(
parameters can be setup
)
.Terminal “8” open
(
high potential
)
,genset stop after
Remote Stop Delay
(
parameters can be setup
)
.
8.2.1.6 Remote start & stop normally closed
In the “Remote mode ”,After Terminal “8” is open
(
high potential
)
,genset start after remote
start delay
(
parameters can be setup
)
.Terminal “8” close
(
low potential
)
,genset stop after
Remote Stop Delay
(
parameters can be setup
)
.
8.2.2 Set Input
Terminal “13” and Terminal “14” has “self-definition selective input” function
;
KP310_1.00 controller has the following set input function.
No. Contents
Note
1
0-Warning Normally
Open
2
1-Warning Normally
Closed
3
2-Stop normally open
4
3-Stop normally closed
Normally Open
:
in the default state, input signal
open
(
high potential
);
input signal close
(
low potential
)
is valid
;
Normally Closed
:
in the default state, input
signal close
(
low potential
);
input signal open
(
high potential
)
is valid
;
8.2.2.1 Warning Normally Open
After Terminal is closed
(
low potential
)
, Warning alarm. Relevant set input faults LED light up.
After Terminal is open
(
high potential
)
, the Set Input faults is eliminated.
8.2.2.2 Warning Normally Closed
After Terminal is open
(
high potential
)
, Warning alarm. Relevant set input faults LED light up.
After Terminal is closed
(
low potential
)
, the Set Input faults is eliminated.
8.2.2.3 Stop normally open
After Terminal is closed
(
low potential
)
,confirmed by Set Input Fault Delay, stop the alarm
immediately, relevant set input faults LED light up.