1. Names of Main Parts and Components

1. Control panel

KGE12E control panel

KGE12E3 control panel

- -

Starting Switch

Timer

Voltage Meter

Breaker

Overload Protector

Single Receptacle

Earthing

Starting Switch

Timer Voltage Meter Breaker

Three-phase Receptace

Earthing

Single Receptacle

9. 

APPENDIX

Ambient temperature

25

1. The choice of the electric cable

The choice of the electric cable depends on the allowable current of the cable 
and the distance between the load and the generator. And the cable section 
should be big enough.
If the current in the cable is bigger than the allowable current, it will become over 
hot and the cable will be burnt. If the cable is long and thin, the input voltage of 
the electric appliance will be not  enough, causing that the generator doesn't start.
In the following formula, you can calculate the value of the potential "e".

The relations among of the allowable current, and length, section of the Insulating 
cable (single core, multi-core) are as follow:
(Presume that the use voltage is 220V and the potential is below 10V.

Potential (v)

=        

                      

Current (A)

  3

Length

Section area

1

58

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

No.

Copper

cables model

2

1.5mm

2

2.5mm

2

4mm

2

6mm

2

10mm

2

16mm

2

25mm

2

35mm

2

50mm

2

70mm

2

95mm

2

120mm

2

150mm

2

185mm

2

240mm

Voltage

Drop

mv/M

Single core

Current capacity

(25 )(A)

Voltage

Drop

mv/M

Three cores

Current capacity

(25 )(A)

Voltage

Drop

mv/M

Four cores

Current capacity

(25 )(A)

VV22

20

28

38

48

65

88

113

142

171

218

265

305

355

410

490

YJV22

25

35

50

60

85

110

157

192

232

294

355

410

478

550

660

30.86

18.9

11.76

7.86

4.67

2.95

1.87

1.35

1.01

0.71

0.52

0.43

0.36

0.3

0.25

VV22

13

18

24

32

45

61

85

105

124

160

201

235

275

323

381

YJV22

18

22

32

41

55

75

105

130

155

205

248

292

343

400

480

30.86

18.9

11.76

7.86

4.67

2.6

1.6

1.2

0.87

0.61

0.45

0.36

0.3

0.25

0.21

VV22

13

18

25

33

47

65

86

108

137

176

217

253

290

333

400

YJV22

13

30

32

42

56

80

108

130

165

220

265

310

360

415

495

VV22

20

28

38

48

65

88

113

142

171

218

265

305

355

410

490

Note: 

The variation of temperature and the laying of cables will influence the current capacity

of cables, the table above is just used for reference.

Summary of Contents for KGE12E

Page 1: ...WUXI KIPOR POWER CO LTD R Single phase KGE12E KGE12EA KGE13EA GASOLINE GENERATOR Three phase KGE12E3 KGE12EA3 KGE13EA3...

Page 2: ......

Page 3: ...h close to the fire this may touch off fire hazard or explosion The extinguisher and first aid kit should be set in the working field 1 Use SAE 10W 30 15W 40 above CD grade lubrication oil Please repl...

Page 4: ...0 the modified coefficient is C 0 04 Counting example When the rated power of generator is P 5KW altitude is 1000m ambient N temperature is 35 relative humidity is 80 the rated power of generator is P...

Page 5: ...as follow Presume that the use voltage is 220V and the potential is below 10V Potential v Current A 3 Length Section area 1 58 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 No Copper cables model 2 1 5mm 2 2 5...

Page 6: ...KGE12EA KGE13EA digital control panel KGE12EA3 KGE13EA3 digital control panel Control Panel Emergency Knob Starting Switch Single Receptacle Overload Protector Fuse Breaker Control Panel Emergency Kn...

Page 7: ...22 6 KGE12E3 ELECTRICAL WIRING DIAGRAM Without Electric Governing DOUBLE VOLTAGE OUTPUT 3 2 Outline drawing of gen set Bracket Protecting Plate Control Panel Output Connection Box Wheel...

Page 8: ...2V 36Ah 370 Digital panel 78 25 4 5 910 600 620 168 Open frame E General panel EA Digital panel Rated Frequency Rated Power Max Power Rated Voltage Rated Current Rated Rotation Speed Alternator model...

Page 9: ...ital panel 78 25 4 5 910 600 620 168 E3 General panel EA3 Digital panel Open frame Rated Frequency Rated Power Max Power Rated Voltage Rated Current Rated Rotation Speed Alternator model Pole Phase Ex...

Page 10: ...e fuel matches gunpowder fuel wetting rags hay and other inflammable and explosive goods from the generator Make sure that nobody near the generator is warned before starting the gasoline generator Do...

Page 11: ...of generator set adopts advanced technique without maintenance Observe the battery indicator light when check the battery Blue the electricity is enough Red the electricity is not enough need to charg...

Page 12: ...service 6 Check the nuts and screws for looseness Check the nuts and screws for looseness if loose tighten them Specially check the air filter muffle and charging alternator Pay attention to the conne...

Page 13: ...r CAUTION CAUTION 2 Simple trouble judge and maintain Immediately stop running generator for check and repair if any abnormality is found Restart after checking and maintain Continue running abnormal...

Page 14: ...analog accord with IEC245 4 Limit length of electric line when using the extension line or distributed network is less than 60m for cables of 1 5mm2 and less than 100m for cables of 2 5mm2 CAUTION CA...

Page 15: ...c When the problem has been solved after stopping the generator you should reset the Emergency stop button before restarting the machine rotate the Emergency stop in the arrow direction and the button...

Page 16: ...long storage refer to the 2 Pre start preparations before restart the generator About the engine refer to the engine manual 1 Button function Setting of various electric parameters display in circle...

Page 17: ......

Page 18: ...KGE12E3 ELECTRICAL WIRING DIAGRAM KGE12E3 ELECTRICAL WIRING DIAGRAM...

Page 19: ...KGE12E ELECTRICAL WIRING DIAGRAM KGE12E ELECTRICAL WIRING DIAGRAM...

Reviews: