
-25-
1
6
9
11
12
13
15
17
24
CONTENTS
1. Names of Main Parts and Components
2. Preparatory Steps for Operation
3. Start and Run the generator set
4. Stop Procedure
5. Lon-term Storage
6. Control panel Function
7. Periodic Maintenance and Service
8. Electric diagram
9. Appendix
The conditions of generator rated output:
Altitude: 0 m Ambient temperature: 25
Relative humidity: 30%
Ambient modified coefficient: C (Relative humidity 30%)
Note: When the relative humidity is 60%, the modified coefficient is C-0.01
When the relative humidity is 80%, the modified coefficient is C-0.02
When the relative humidity is 90%, the modified coefficient is C-0.03
When the relative humidity is 100%, the modified coefficient is C-0.04
Counting example:
When the rated power of generator is P =5KW, altitude is 1000m, ambient
N
temperature is 35
, relative humidity is 80%, the rated power of generator is:
P=P
(C-0.02) = 5
(0.82-0.02) = 4KW
N
2. Modified coefficient table of ambient condition power
Ambient temperature (
)
Altitude
(m)
0
500
1000
2000
3000
4000
25
1
0.93
0.87
0.75
0.64
0.54
30
0.98
0.91
0.85
0.73
0.62
0.52
35
0.96
0.89
0.82
0.71
0.6
0.5
40
0.93
0.87
0.80
0.69
0.58
0.48
45
0.90
0.84
0.78
0.66
0.56
0.46
CAUTION
Electrical equipment (including electrical lines and plugs connection) could not
be defective. By the effect of mechanical stress, make sure to use the rubber
sheathed flexible cable or analog.
Limit length of electric line when using the extension line or distributed
network is: less than 60m for cables of 1.5mm2, and less than 100m for
2
cables of 2.5mm