background image

 Page 6 of 12

2.2.3.1 SOLAR CONNECTIONS: SINGLE COIL

The flow and return from the solar heat source are to be connected to the lower coil. Either primary coil connection may be 

utilised as the flow or return. The solar sensor, supplied as part of the solar controls, is inserted into the sensor well above the 

solar coil and is held in place with the black sensor well retaining bung provided. 

2.2.3.2 SOLAR CONNECTIONS: TWIN COIL

In a solar thermal system the lower coil is connected to the solar heat source. Either primary coil connection may be utilized as 

the supply or return. The solar tank sensor, supplied as part of the solar controls, inserts into the sensor well above the solar 

coil.

The upper boiler coil will be connected to the boiler as per the manufacturers’ instructions. Ideally boiler thermostat should be 

located in a sensor well above the coil position. 

2.2.4 HOT WATER PIPEWORK

Run the first part of the hot water distribution pipework in ¾” . This can be reduced to the appropriate size for the type of faucet 

etc. Your aim should be to reduce the volume of the hot draw-off pipework to a practical minimum so that the time taken for 

the hot water is as quick as possible. Do not use monobloc mixer faucet or showers if the balanced cold connection is not 

provided. Outlets of this type can back pressurize the unit and result in discharge. 

The use and installation of an ASSE approved thermostatic mixing valve is required. 

The suggested location for this valve may be seen in section 2.2 Figure 2. 

2.2.5 TEMPERATURE AND PRESSURE RELIEF VALVE

The hot water tank must be installed with an appropriate temperature and pressure relief valve.  The hot water tank has a 

¾”NPT female connection to accommodate this apparatus in the top of the tank.

CAUTION: To reduce the risk of excessive pressures and temperatures in this water heater, install temperature and pressure 

protective equipment required by local codes but no less than a combination pressure valve certified as meeting the 

requirements for Relief Valves and Automatic Gas Shutoff devices for Hot Water Supply Systems ANSI Z21.22.

The T&P valve must be connected to a discharge pipe. This pipe must:

•  Terminate a maximum 6” above a floor drain. In the rare event of a discharge the water will be very hot and may be  

 

  combination of water and steam, at pressure. Care must be taken to safely route the discharge pipe safely to drain.

•  Be no smaller than ¾” diameter and must not be reduced in size.

•  No other valve can be placed on the discharge line between the T&P valve and the discharge exit.

•  The pipe must be capable of withstanding 250˚F.

•  The pipe must be compiled of straight runs, direct to drain, to allow complete drainage of the valve and pipe assembly.

•  The relief valve connections should not be used for any other purpose.

2.2.2 CONNECTING TO THE TANK

All of the water carrying pipe connections on the tank are ¾”  NPT male. Suitable jointing compound that is suitable for potable 

water and hot water should be used to provide a watertight seal.

2.2.3 COIL CONNECTIONS

The coil connections to the boiler or solar circuit are ¾”  NPT male. Ensure good connections. Use commercially accepted 

water inhibitors as stated by the manufacturer of the boiler or renewable energy system.

WARNING

The expansion tank is an important safety feature of the tank installation. It must be installed and properly sized.  Refer to 

Table.2 for Kingspan supplied sizes.

Volume

Minimum expansion tank size

58/60Gal

5Gal 

80Gal

7Gal 

119Gal

10Gal 

Table.2

 Expansion SIzing

Summary of Contents for Tribune

Page 1: ...IMPORTANT NOTE TO THE INSTALLER Read these instructions before commencing installation Installation Manual For Kingspan Tribune USA Issue 4 Sept 2010 Part No BOOKSTAINULT Page 1 of 12 Tribune ...

Page 2: ...ate this water heater if it is not working properly or if it has been damaged or dropped 8 This water heater should be serviced only by qualified service personnel Contact nearest authorized service facility for examination repair or adjustment SAVE THESE INSTRUCTIONS DANGER Very Hot Water can cause serious injury or death Ensure that you comply with the instructions contained within this manual a...

Page 3: ...t maximum of 2 The pan should be connected to drain by a bore drain Consult a certified plumber for more information The KINGSPAN TRIBUNE should be located near to a drain to allow the drainage of water during maintenance and as an outlet for the safety equipment located on the unit The KINGSPAN TRIBUNE tank can supply outlets above it or at some distance from it Site the unit to minimise dead leg...

Page 4: ...s allows a variety of heat sources to be used In the single coil configuration this can be connected to a boiler or solar circuit Twin coil tanks the lower coil is connected to a solar circuit and the top coil to a boiler system Figure 1 shows a schematic of the tank configuration Page 4 of 12 Figure 1 Single and Twin coil configurations ...

Page 5: ...d water system meaning that thermal expansion may cause a pressure build up within your hot water tank In such a case an expansion tank must be fitted to allow for any excess pressure caused by thermal expansion Please see figure 2 for reference Water pressure If the incoming water pressure is over 80 PSI a pressure reducing valve Water pressure regulator must be fitted This is to be located on th...

Page 6: ...e The hot water tank has a NPT female connection to accommodate this apparatus in the top of the tank CAUTION To reduce the risk of excessive pressures and temperatures in this water heater install temperature and pressure protective equipment required by local codes but no less than a combination pressure valve certified as meeting the requirements for Relief Valves and Automatic Gas Shutoff devi...

Page 7: ...r the immersion heater current load The unit must be grounded to a properly installed ground circuit using an appropriate field terminal Check the immersion heaters are 240V and rated at 4500W this should be stated on the case Figure 3 shows the layout and wiring schematic of the heating element To access the wiring terminals firstly remove the temperature dial by gently pulling of the dial comple...

Page 8: ...pen every other hot faucet in turn to purge all remaining air 3 1 FILLING If the tank is to be heated by an indirect boiler consult the boiler manufacturers commissioning instructions and fill the primary circuit accordingly Two port valves and tank thermostats may need to be used to control input into the KINGSPAN TRIBUNE unit 3 2 INDIRECT UNITS During heat up there should have been no sign of wa...

Page 9: ...3 4 INSTALLATION CHECKLIST FLOW CHART Page 9 of 12 Figure 4 Check list of installation steps ...

Page 10: ...me as the annual boiler or solar system service 1 Lift the lever on the expansion relief valve on the inlet control set and allow water to flow for 5 seconds Release and make sure it resets correctly Repeat with the pressure temperature relief valve In both cases check that the discharge pipe work is carrying the water away adequately If not check for blockages etc and clear WARNING THE WATER DISC...

Page 11: ...er than by kingspan It has not been misused tampered with or subjected to neglect It has only been used for the storage of potable water It has not been subjected to frost damage The unit has been serviced annually The guarantee period starts from the date of purchase and no registration is required The guarantee is not transferable and rests with the original householder The system is fed from a ...

Page 12: ......

Reviews: