User Instruction Manual

Kingspan SafePro 2 

Anchor and Cable System

11.0 The SafePro 2 Cable System

11.1 The Kingspan SafePro 2 Cable System

The SafePro 2 Cable System consists of a 8mm (5 / 16”) Stainless Steel horizontal mounted lifeline. The system is fixed to the structure 
via SafePro 2 Anchors. The lifeline may be supported at regular intervals by intermediate  brackets. The intermediate brackets help to 
reduce the loads in the event of a fall and allow for longer single installations.
The System offers both fall arrest and restraint capabilities. The System allows users to attach and detach at any point on the cable 
and move over the Corner / intermediate brackets without interruption.
The Cable has a minimum breaking strength of 38 kN (8,550 lbs) and can span up to 15 metres (48.2 ft) between intermediate 
supports.
The SafePro 2 Cable System is designed to provide a facility to enable safe working at heights in accordance with current regulations.
The System has been tested and conforms to the requirements of: EN 795:2012 TYPE C, TS 16415:2013 TYPE C.

11.2 Positioning the SafePro 2 Cable System

When positioning the SafePro 2 Cable System there are two styles of placement to consider.

3M™ DBI-SALA

®

 RoofSafe Anchor and Cable System

The RoofSafe Anchor
Section 2.0

4

2.1 

The 3M™ DBI-SALA

®

 RoofSafe Anchor 

The 3M DBI-SALA RoofSafe Anchor provides a secure anchor point for a worker at height, close to an exposed edge  
or other fall hazards, when used in conjunction with associated PPE, such as a full body harness and safety lanyard. 

There are two types of Anchors within the range, the SpiraTech Anchor (CE only) and the Tip Over Anchor.  
Both Anchors are modular in design allowing for speed of fitting and use.

The Anchors have been tested and conforms to the requirements of: 

•  EN795 2012 TYPE A 

•  CEN TS 16415:2013 Type A

•  OSHA 1926.502 M

•  ANSI Z359.1 2007 

•  AS / NZS 1891.2

The 3M DBI-SALA RoofSafe Anchors have been designed to re-orientate and deploy an energy absorber in the event of a fall, 
there by reducing the load transferred to the roofing system as compared to a rigid anchor. The Anchors can be used for both fall 
arrest and work restraint applications. 

The Anchors can be installed on standing seam, bituminous and PVC membrane, composite / built up and membrane and fragile 
roofing systems. 

Both Anchors allow the user to walk 360 degrees around the Anchor without needing to reorientate the lanyard or connectors. 
The Anchor incorporates full weather sealing to combat water ingress, and allows different roof membranes to be fitted  
and sealed around the Anchors for true weather proofing.

SpiraTech Anchor

Single Point Tip 

Over Anchor

Can be used as a single point 
Anchor for up to two users.  
CE Only.

Can be used as a single point 
Anchor for one user. (to conform 
to ANSI please use RA Single 
Point Eye AM,7241168).

Form No: 5903917   Rev: D

3M™ DBI-SALA

®

 RoofSafe Anchor and Cable System

The RoofSafe Anchor
Section 2.0

4

2.1 

The 3M™ DBI-SALA

®

 RoofSafe Anchor 

The 3M DBI-SALA RoofSafe Anchor provides a secure anchor point for a worker at height, close to an exposed edge  
or other fall hazards, when used in conjunction with associated PPE, such as a full body harness and safety lanyard. 

There are two types of Anchors within the range, the SpiraTech Anchor (CE only) and the Tip Over Anchor.  
Both Anchors are modular in design allowing for speed of fitting and use.

The Anchors have been tested and conforms to the requirements of: 

•  EN795 2012 TYPE A 

•  CEN TS 16415:2013 Type A

•  OSHA 1926.502 M

•  ANSI Z359.1 2007 

•  AS / NZS 1891.2

The 3M DBI-SALA RoofSafe Anchors have been designed to re-orientate and deploy an energy absorber in the event of a fall, 
there by reducing the load transferred to the roofing system as compared to a rigid anchor. The Anchors can be used for both fall 
arrest and work restraint applications. 

The Anchors can be installed on standing seam, bituminous and PVC membrane, composite / built up and membrane and fragile 
roofing systems. 

Both Anchors allow the user to walk 360 degrees around the Anchor without needing to reorientate the lanyard or connectors. 
The Anchor incorporates full weather sealing to combat water ingress, and allows different roof membranes to be fitted  
and sealed around the Anchors for true weather proofing.

SpiraTech Anchor

Single Point Tip 

Over Anchor

Can be used as a single point 
Anchor for up to two users.  
CE Only.

Can be used as a single point 
Anchor for one user. (to conform 
to ANSI please use RA Single 
Point Eye AM,7241168).

Form No: 5903917   Rev: D

End/Corner Anchor

Can be used as a single point Anchor for up to 

two users. 

Single Point Tip Over Anchor

Can be used as a single point Anchor for one 

user.

Work Restraint 

 

A Restraint System is designed to prevent a 
user accessing risk areas (such as roof edges), 
thereby preventing a fall.

Fall Arrest 

A Fall Arrest System allows access to a fall 
hazard and is designed to safely arrest the 
operative in the event of a fall.

01

02

Important Note:

Whilst all Anchor installations must be designed for Fall Arrest in case of accidental misuse, it is 
recommended that the positioning of the Anchor should be located for Work Restraint. Restraint 
enables a user to access  their work area whilst being prevented from gaining  access to a fall 
hazard and  will reduce risk and mitigate against the consequences of a fall.

Summary of Contents for SafePro 2

Page 1: ...Kingspan SafePro 2 Anchor and Cable System User Instruction Manual Fabrications Safety Lighting solutions UK Ireland...

Page 2: ...Maintenance Check List Anchor 14 10 0 Foreword Cable 15 11 0 The SafePro 2 Cable System 16 11 1 The Kingspan SafePro 2 Cable System 16 11 2 Positioning the SafePro 2 Cable System 16 Contents 12 0 Syst...

Page 3: ...n certified Installer or competent persons trained by Kingspan or Kingspan s representative and must be in accordance with Kingspan s technical instructions and all prevailing national standards All u...

Page 4: ...gid anchor The Anchors c arrest and work restraint applications The Anchors can be installed on standing seam bituminous and PVC membrane composite built up and roofing systems Both Anchors allow the...

Page 5: ...all 3M DBI SALA RoofSafe Anchor and Cable System The RoofSafe Anchor Section 2 0 2 2 Positioning of the 3M DBI SALA RoofSafe Anchor When positioning the 3M DBI SALA RoofSafe Anchor System there are tw...

Page 6: ...all the tools and information required to successfully install and test the product Included in this manual is a checklist of the minimum amount of information that should be supplied by the installe...

Page 7: ...fixings The Anchor s must not be used as a lifting system Do not use the Anchor for equipment tie back Never exceed the recommended number of users on the Anchor See label on product or system tag Ne...

Page 8: ...s bitumen cement chloride paint or aggressive cleaning fluids Stainless Steel parts are particularly susceptible to pitting corrosion from chlorine so avoid exposure in this type of environment If the...

Page 9: ...implements must also be avoided Preferably fall arrest equipment like this should when not required for use be kept in dedicated cabinets which permit adequate ventilation 6 0 Pre Use In Use Checks 6...

Page 10: ...r cross members that are not shaped in a way that can capture the gate of the hook 3M DBI SALA RoofSafe Anchor and Cable System Pre Use In Use Checks Section 6 0 10 6 3 Compatibility of Components If...

Page 11: ...g lanyard to the rear D ring of the harness This prevents the lanyard getting in the way during use Always ensure make compatible connection only Always ensure that the locking mechanism of the carabi...

Page 12: ...gistration card Recorded and indicated the minimum ground clearance Provided the contact details of Kingspan Provided the contact details of the Installation company The maximum number of users permit...

Page 13: ...minous Membrane Roof Composite Built Up Roof PVC Membrane Roof Form No 5903917 Rev D 3M DBI SALA RoofSafe Anchor and Cable System Typical Anchors Section 8 0 13 Standing Seam Roof Anchor Bituminous Me...

Page 14: ...rectly tightened Use Torque Wrench as required Proof load test concrete fixings to 6kN Clean system as necessary Check Attachment Devices operate correctly Cable Systems Check cable condition for fret...

Page 15: ...should be conducted by a Kingspan certified Installer or competent persons trained by Kingspan or Kingspan s representative and must be in accordance with the Kingspan s technical instructions and all...

Page 16: ...sealed around the Anchors for true weather proofing SpiraTech Anchor Single Point Tip Over Anchor Can be used as a single point Anchor for up to two users CE Only Can be used as a single point Anchor...

Page 17: ...he product Included in this manual is a checklist of the minimum amount of information that should be supplied by the installer following the installation of your Anchor s 12 3 Fixings It is imperativ...

Page 18: ...sting the Anchor and fixings The System must not be used for lifting Do not use the system for equipment tie back Never exceed the recommended number of users on the system See label on product or sys...

Page 19: ...e system with acids bitumen cement chloride paint or aggressive cleaning fluids Stainless Steel parts are particularly susceptible to pitting corrosion from chlorine so avoid exposure in this type of...

Page 20: ...s kinks or excessive sag in the cable or damaged brackets Turn the disc attached to the tensioner If the disk does not turn contact your Installer for advice Check the legibility of all markings on an...

Page 21: ...ty If necessary the user should use other safety equipment such as a twin tailed lanyard to facilitate safe access to the attachment area 16 3 Attaching to the System The slider is designed in such a...

Page 22: ...point of the UniGrab should be facing towards the side you want to walk on 16 4 Working on both sides of the 3M Fall Protection System To remove the UniGrab reverse the procedure on page 9 If you wish...

Page 23: ...the installation A unique identification number The number and length of systems The maximum number of users per span and per system The length and type of lanyards The installation date The date of...

Page 24: ...NOTES 1 MATERIAL 031 004 0 8mm 0 1mm ALUMINUM 5005 2 FINISH ANODIZED SCREEN PRINTED BLACK BLUE Pantone 2748 LOW TEMPERATURE BAKED USE THE CURRENT REVISION OF FILE 7241184 ai FOR LABE L GEOMETRYAND ART...

Page 25: ...nents SYSTEMEYE PIN SafePro 2 System Eye Pin CORNER90 8mm 90 Corner TOGGLE8mm 8mm Hex Swage Toggle TENSIONER8mm 8mm 0 8 kN Hex Swage Tensioner CORNER45 8mm 45 Corner SLIDER CAR8mm 8mm UniGrab Carabine...

Page 26: ...rectly tightened Use Torque Wrench as required Proof load test concrete fixings to 6kN Clean system as necessary Check Attachment Devices operate correctly Cable Systems Check cable condition for fret...

Page 27: ...n to deal with such emergencies cannot be overemphasized Such a plan includes consideration of rescue equipment personnel and training as necessary It is not acceptable just to rely on the emergency s...

Page 28: ...r markets please contact your local sales representative or visit www kingspanpanels com Care has been taken to ensure that the contents of this publication are accurate but Kingspan Limited and its s...

Reviews: