Type of Safety Device
Operating Condition
Release/Reset
1SFTTVSF3FMJFG7BMWF 8BUFSTJEFTFF'JH
300 kPa
Self Reset
'MPX4XJUDI 8BUFSTJEFTFF'JH
> 8 l/min
< 6 l/min
)JHI5FNQFSBUVSF5IFSNPTUBU TFF'JH
> 120 °C
< 90 °C
3FGSJHFSBOU5FNQFSBUVSF4FOTPST 'JH5UP5
'BJMVSF0VUPG3BOHF
( Operating range depends on sen-
sor location)"
In Range
8BUFS5FNQFSBUVSF4FOTPST 'JH5B5C
T < 0 °C, T > 70 °C
0 °C ≥ T ≤ 70 °C
"OUJ'SFF[F1SPUFDUJPO 'JH5
Adjustable from 2 to 6 °C
Software controlled
Compressor Start Acceleration limit
6 accelerations/hr
N/A
%FMBZFE$PNQSFTTPS4UBSU 0''0/
180 secs (max)
N/A
%FMBZFE$PNQSFTTPS4UPQ 0/0''
180 secs
N/A
IMPORTANT
During functioning in heat pump heating mode, the unit performs defrost cycles to eliminate any ice that might
form at low temperatures inside the outdoor unit
!
Refrigerant charge check
This check becomes necessary after any refrigerant leak
or after replacement of the compressor.The best method
to correctly charge refrigerant is to completely empty the
refrigerant circuit using refrigerant recovery equipment.
Then charge the exact quantity of refrigerant according
to the data shown on the unit nameplate and always
considering the additional charges listed on the charge
sheet.
R-410A systems must be charged with liquid refrigerant. Use
the special recharging equipment (normally on the market)
to control the refrigerant correctly.
!
IMPORTANT
Any works carried out on the refrigerant circuit
must be undertaken by a person holding the
relevant Fgas certification
A: 4 way valve
B: DC Rotary Compressor
C: BPHE
D: Pulse Motor Valve
E: Distributor
''BO
G: Heat Exchanger
HTT: High Temperature Thermostat
T1: TS sensor
T2: TD sensor
T3: TR sensor
T4: TE sensor
T5: TO sensor
Ta: EWT sensor
Tb: LWT sensor
25
A
B
C
D
E
F
G
14