background image

10

Venting Routes And Components

Since it is very important that the vent system maintain its balance
between the combustion air intake and the flue gas exhaust, certain lim-
itations as to vent configurations apply and must be strictly adhered to.

The table showing the relationship between vertical and horizontal side
wall venting will help to determine the various vent lengths.

The maximum horizontal vent run with the 90 degree bend to the fire-
place flue outlet is 3 feet (91cm) Figure 1. The maximum horizontal
vent run is 10 feet (305cm) when the vertical rise is 8 feet (244cm)
Figure 2. Note: 1/4” vertical rise is required for every 12” of horizontal
run.

The maximum number of 90 degree bends per side wall installation is
one (1).

The maximum number of 45 degree bends per side wall installation is
two (2). These bends can be installed in either the horizontal or vertical
run.

Maximum vertical rise is 20 feet (6.09 meters).

Special Note: For each 45 degree bend installed in the horizontal
run, the length of the horizontal run must be reduced by 18”
(45cm). This does not apply if the 45 degree bends are installed on
the vertical part of the vent system.

Example: 

If according to the table, the length of the horizontal run is

10 feet, and two 45 degree bends are required, the horizontal run length
must be reduced to 7 feet.

How To Use The Vent Table

1. Determine the height of the system and the number of bends

required.

2. Having determined the vertical distance determine the maximum

horizontal section allowed.

3. Vent table has been established for 90˚ horizontal/vertical runs.

With use of flex pipe distance not having 90˚ bends will not fall into
vent table standards. See Fig. B.

Venting Table For Top Vent Models

for venting to a maximum of 20 ft. (6.09meters)

Sidewall or Vertical Venting (See Fig. A & B)

Total Vertical

Max Total Horizontal

Feet

Meters

Feet Meters

4

1.2

3

0.9

5

1.5

4

1.2

6

1.8

6

1.8

7

2.1

8

2.4

8

2.4

10

3.0

9

2.7

11

3.4

10

3.0

12

3.7

11

3.4

13

4.0

12

3.7

14

4.3

13

4.0

15

4.6

14

4.3

16

4.9

15

4.6

15

4.6

16

4.9

14

4.3

17

5.2

13

4.0

18

5.5

12

3.7

19

5.8

11

3.4

20

6.1

10

3.0

Example A:

If the vertical dimension from
the floor of the fireplace is
6.5ft, the horizontal run to the
wall flange of the vent termi-
nation must not exceed 7.5ft.

NOTE: The final location of
the fireplace must be such
that the horizontal vent
dimensions fall within those
stated on the graph. The
Maximum Vertical vent run is
20 feet (6.09meters).

Important: 

Always locate the fireplace in such a way that a minimum of off-

sets and/or horizontal runs are required. 1/4” vertical rise is required for every
12”  horizontal run.

Important: 

Minimum clear-

ance between vent pipes and
combustible materials is 1 inch
(25mm).

7.5

6.5

Summary of Contents for "Zero Clearance" ZDV1001

Page 1: ...nce What To Do If You Smell Gas Do not try to light any appliance Extinguish any open flame Do not touch any electrical switch Do not use any phone in your building Immediately call your gas supplier...

Page 2: ...8 Vent termination 9 10 Venting graph 10 General vent installation information 11 Installation of top flue side wall venting 11 12 Installation of back vents 13 Repair parts list 13 Valve System Part...

Page 3: ...vice person A professional service person should be called to inspect this appliance annually Make it a practice to have all your gas appliances checked annually 6 Control compartments burners and air...

Page 4: ...llation recommendation when installing this fire place against non insulated exterior wall or chase it is recommend ed that the outer walls be insulated to conform to applicable insula tion codes Dryw...

Page 5: ...pressure testing of the gas supply piping sys tem at test pressures equal to or less than 1 2 PSIG 3 5 KPa Note The gas line connection may be made of 1 2 rigid pipe 1 2 copper pipe or an approved fl...

Page 6: ...should any solid fuels wood paper card board coal be used in this appliance Note It is normal for your gas fireplace to give off some odor the first time it is burned This is due to the curing of the...

Page 7: ...plug on the inside wall of the access area opposite the fan Large holes are provided to allow wiring to enter the access area on the left of the unit Connect the power sensor and variable speed wall...

Page 8: ...that turns the main burner on or off If main burner does not light immediately when you turn the gas control valve to ON ensure that the wall switch is in the ON position NOTE The On Off wall switch...

Page 9: ...driveway located on public property 7 feet 2 1m minimum 3 V NOTE Clearances are to the terminal center line Add 6 inches to clearances not indicated as measured from center line NOTE Local Codes or R...

Page 10: ...s are required the horizontal run length must be reduced to 7 feet How To Use The Vent Table 1 Determine the height of the system and the number of bends required 2 Having determined the vertical dist...

Page 11: ...ing on the wall Cut a hole through the exterior wall allowing for a 11 x 11 minimum inside framing or an 8 1 2 diameter hole if venting through a non combustible wall Center wall thimble over 11 x 11...

Page 12: ...NOTE At the top edge of the flashing plate lift the shingles and nail the plate to the roof deck then cement the shingles to the plate with a suitable waterproof mastic Ensure that the chimney is plum...

Page 13: ...d must be cut to comply Install wall thimble Place fireplace into place and secure to floor with nailing tabs Step 5 Mount vent termination make sure 4 and 7 pipes are siliconed Caulk around wall thim...

Page 14: ...urround Kits ZISAB Surround Antique Brass ZISPB Surround Polish Brass ZISAL Surround Almond ZISBG Surround Burgundy ZISGR Surround Green ZISSAB Surround Slim Line Antique Brass ZISSPB Surround Slim Li...

Page 15: ...h ON wall switch If okay jumper wires across wall switch wires at valve If burner comes on wires are faulty or connections are bad Generator may not be generating Check generator with millivolt meter...

Page 16: ...ing its stability or performance d damages caused by improper matching or application of the unit or the unit s components e damages caused by failing to provide proper maintenance and service to the...

Reviews: