ZCV42
Framing Dimensions
Determine whether face of fireplace will be:
•
Flush with finished wall (e.g., for surround, cultured stone or other non combustible covering).
•
Flush with framing (to be covered with concrete board for a Flat Wall appearance).
Refer to Nailing Tab Guide section also.
52-1/2” MIN for NG
64-1/2” MIN for LP
Plus Rise of 1/4” Per
Foot*
Fig.1
Framing for Horizontal Vent
Termination
(See
Installation of Side
Wall Venting
Section)
Vertical Venting MUST maintain 1” clearance to combustibles.
These structures are not load bearing.
Fig. 1
Recessed Combustible Wall
RIGHT SIDE
*For Propane Horizontal installations the venting must be an additional one foot above
the minimum vertical rise off the flue before going horizontal.
Framing Depth:
19” from back wall to
face of fireplace.
18-1/2” for Drywall flush
with face of unit.
17