GAS LINE INSTALLATION

1. The gas pipeline is brought into the unit on the back left side of the unit.
2. The gas control inlet is 3/8".  Typical installation layout for rigid pipe is shown below.
3. When using copper or flex connector, use only approved fittings.  Always provide a union so that gas line

can be easily disconnected for burner or fan servicing.  See gas specification for pressure details and ratings.

4. When a vertical section of gas pipe is required for installation, a condensation trap is needed. 

See CAN/CGA-B149.1 or .2 for code details.

5. For natural gas, a minimum of 3/8" iron pipe with gas minimum pressure of 4.5" w.c. must be used for supply

from the gas meter.  Consult with the local gas utility if any questions arise concerning pipe sizes.

6. 1/8" NPT plugged tappings are accessible for test gauge connection both on the inlet and outlet of the gas

valve.

7. Turn the gas supply ON and check for leaks.  DO NOT USE OPEN FLAME FOR THIS PURPOSE.  Use an

approved leak testing solution.

8. The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during

any pressure testing of that system at test pressures in excess of 1/2 PSIG (3.5 KPa).

9. The appliance must be isolated from the gas supply piping system by closing its individual shutoff valve

during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG
(3.5 KPa).

NOTE: The gas line connection may be made of 1/2" rigid pipe or an approved flex connector.  Since some
municipalities have additional local codes, it is always best to consult your local authorities and the current
CAN/CGA-B149.1 or .2 installation code in Canada or the National Fuel Gas code ANSI Z223.1 in the U.S.A.

For the state of Massachusetts a 

T-handle gas shut-off valve

must be used on a gas appliance.  This T-handle gas

shut-off valve must be listed and approved by the state of Massachusetts.  This is in reference to the state of
Massachusetts state code CMR238.

This gas appliance should be installed by a qualified installer in accordance with local building codes and with current
CAN\CGA-B149.1 or .2 installation codes for Gas Burning Appliances and Equipment in Canada and the National
Fuel Gas Code Z223.1 in the United States.

NOTE: IF THE OPTIONAL FAN KIT IS TO BE INSTALLED IT IS HIGHLY RECOMMENDED THAT IT
BE ATTACHED TO THE STOVE BEFORE THE STOVE IS PUT IN ITS FINAL POSITION.

6

IMPORTANT: Always check for gas leaks with a soap and water solution.

Do not use open flame for leak testing.

f i r e - p a r t s . c o m

Summary of Contents for FV5000

Page 1: ...Co Inc 2340 Logan Ave Winnipeg Manitoba Canada R2R 2V3 Ph 204 632 1962 Read this complete manual before beginning installation These instructions must be kept with the unit for future reference FOR Y...

Page 2: ...ever due to the high temperature silicone components the paint will cure when heat is applied to the appliance as it is first used The following information applies to the curing process to get the pa...

Page 3: ...intenance instructions 7 General glass information 8 Log assembly 9 Log placement 10 11 Optional fan kit installation 12 Millivolt system lighting burner control 13 Vent installation 14 Accessory list...

Page 4: ...temperatures and should be located out of heavy traffic areas and away from furniture and draperies 2 Children and adults should be alerted to the hazards of the high surface temperatures of this appl...

Page 5: ...tockings or decorations be hung from it 9 Under no circumstances should any solid fuels wood paper be used in this appliance 10 For safe operation purge gas line with glass door removed to assure a co...

Page 6: ...of 1 2 PSIG 3 5 KPa 9 The appliance must be isolated from the gas supply piping system by closing its individual shutoff valve during any pressure testing of the gas supply piping system at test pres...

Page 7: ...ts burners and air passages in this appliance should be kept clean and free of dust and lint Make sure that the gas valve and pilot light are turned off before you attempt to clean this unit 7 WARNING...

Page 8: ...reas This appliance should not be used as drying rack for clothing nor should Christmas stockings or decorations be hung near it Under no circumstances should any solid fuels wood paper cardboard coal...

Page 9: ...imately 1 8 to all four sides of frame and insert glass with new gasket Frame should be placed on a flat surface with a small amount of weight pressing glass into sealant Let dry approximately 15 to 2...

Page 10: ...log Step 2 Break glowing embers into thumbnail size Place glowing embers evenly on to the front burner Do not go over the grate Step 3 Place front log over front burner with the left right sides agai...

Page 11: ...ded Bark should be to the outside Step 6 Place left crossover log into the slots that are provided Bark should be to the outside Step 7 Purge lines and test pilot operation Step 8 Replace glass door L...

Page 12: ...to position 4 Connect the wires to the sensor and variable speed control as shown in the diagram Connect the fan extension cord to 110volt power 5 Turn the variable speed control to the on position cl...

Page 13: ...push knob in for one 1 minute Release knob Pilot should remain lit If it goes out repeat steps 2 through 5 until pilot remains lit If knob does not pop up when released stop and immediately call your...

Page 14: ...hes or larger Four 4 inch single wall or B Vent liquid fuel gas chimney or Flex Gas Liner may be used to adapt existing chimney or liner to stove When installing with B Vent liquid fuel gas chimney in...

Page 15: ...r 2000 085 Variable Speed Switch Fan 3000 930 Thermo Disc Spill Switch CONVERSION KITS For SIT Valve only 5000V CKLP LP Conversion Kit 5000V CKNG NG Conversion Kit BURNER ASSEMBLY AND VALVE SYSTEM PAR...

Page 16: ...alve Nova NG Hi Lo 0820634 1001 P713SI Pilot Burner LP 199 713 TC SIT 1001 P714SI Pilot Burner NG 199 714 TC SIT If Serial Number is GRETAER than 4740 only SYSTEM 3 New SIT TC True Millivolt Vented 50...

Page 17: ...switch wiring for ground May be grounded to appliance or gas supply Check generator with millivolt meter Take reading at generator terminals of gas valve Should read 325 millivolts minimum while hold...

Page 18: ...ce or maintenance h damage repairs inoperation or inefficiency resulting from faulty installation or application i electricity or fuel costs or any increase in electricity or fuel cost whatsoever incl...

Reviews: