      Page 9 of 15                  King Pigeon Communication Co.,Limited.              Ver 1.5    File No.:RTU5025103 

A Professional GSM 3G M2M products manufacturer 

and automation solution provider, since 2005.

 

www.GSM-Gate-Opener.com    [email protected]

 

6. Setting by SMS commands(

not recommend,for remote setting only

Notice: 

1.  The default Password is 

1234

2.  You can program the RTU5025 with SMS commands using your phone. It is safe to do so because in 

addition to the fact that other people may not know the number of the SIM inserted in it, we also use a 

Password that makes it impossible for others who doesn't know it, to access the system by chance, and 

all the action will be recorded. 

3.  The relay output will change the close or open status by every call in, please note it. Means the first time 

call it, it will close the relay to switch on the lock, if the second call in is in the setting time, then the unit 

will ignore the setting time, and open the relay, to switch off the lock. 

4.  Remember that commands must be 

CAPITAL LETTERS

. It is AA not aa, EE not Ee etc. Don't add 

spaces or any other character on the SMS commands. 

5.  The 

pwd

 in the command means the password,like 1234 or 5678 if you changed. 

6.  If the RTU5025 used for gate access only,all you need to do is to change the default password and add 

the authorized numbers.   

7.  If you cannot call to control the RTU5025 or cannot send or receive any SMS message from it.please try 

to add + in front of the country code or the phone numbers: 

 

 

8.  Export the Authorized number list to .xls/.csv file and keep it for reference in further. 

9. 

Fo security purpose, the RTU5025 will note return any SMS if command error,

so please make sure and 

check the SMS Commands, or add the country code before the telephone number or check the input is 

in ENGLISH INPUT METHOD and CAPS LOCK. 

10. The SMS commands that you will certainly use in the RTU5025 are the following: 

 

 

For example: 

In China, the country code is 

0086

The user cell phone number is 

13570810254

 and has been assigned as 

the SMS Alert number, the simcard number in the panel is 

13512345678

.   

Problem 1:

 Alarm 

but the user hasn’t received the SMS Alert. 

Solution: Please plus the country code while you setup the 13570810254 as SMS Alert number, means setup 

008613570810254 

instead of the 

13570810254

.   

Problem 2:

 The user number can receive the SMS Alert message from alarm panel, but the alarm panel can 

not receive the commands from the user number. 

Solution: Please add country code to the simcard number in the alarm panel. Means send sms commands to 

008613512345678

    instead of 

13512345678

Solution 3:

 Use mobile phone A to call mobile phone B, the number displayed on B is which you should set 

as the dial number; Use mobile phone A send SMS to mobile phone B, the number displayed on B is which 
you should set as the SMS alert number; sometimes you may need to use the 00 to replace the + or use the + 
to replace the 00 on front of the country code. 

Summary of Contents for RTU5025 Series

Page 1: ...ith a FREE call from your mobile phone Remote switching machines with a FREE call from your mobile phone User Manual Ver 1 5 RTU5025 Series Date Issued 2015 03 25 All rights reserved by King Pigeon Co...

Page 2: ...inquiry status historical data IMEI code and firmware version 13 6 6 Data function 14 7 Important information 15 8 Maintenance 15 9 Warranty 15 Caution Please read this user manual carefully before i...

Page 3: ...m authorized number then carries out the turn ON OFF action on the first ring Secure Using Caller ID for verification unknown phone calls are ignored SMS confirmation of relay actions door open to the...

Page 4: ...tors lights pumps generators valves and machines 2 Safety Directions Safe Startup Do not use Gate Opener when using GSM equipment is prohibited or might bring disturbance or danger Interference All wi...

Page 5: ...twork Flash per 2 seonds Normal status OFF can t connect to SIM card or unregistered to the cellular network Connection Terminals Power Power supply input Positive wire Red _ Power supply input Negati...

Page 6: ...M Gate Opener com Support GSM Gate Opener com 4 Typical wiring connection 1 RTU5025 for Gate opener Connect the door sensor to DIN1 for door status detection and siren for alarm sound the lock switche...

Page 7: ...s CP210x USBto UART Bridge for example COM3 Click here to know how to find out the COM Port on your computer 7 Run this configurate software select the COM Port number for example COM3 click Open the...

Page 8: ...format to the PC under the configuration folder Export csv Export the authorized number list csv format to the PC under the configuration folder All Always Select all the numbers as Always can call in...

Page 9: ...you cannot call to control the RTU5025 or cannot send or receive any SMS message from it please try to add in front of the country code or the phone numbers 8 Export the Authorized number list to xls...

Page 10: ...n and always can call in to control E g 1234A016 123456 1502050800 1502051000 to set the phone number 123456 at the 16th position this number can call in to control during Feb 5th 8 00a m 1502050800 t...

Page 11: ...then open OFF after call in 6 3 4 Who will receive the confirmation SMS when the relay is ON OFF for relay ON for relay OFF ab the ID code of the 1st number a and the caller number b 0 means disable...

Page 12: ...out RTU5025 will call the 1st number and next number if there have no answering 6 4 1 Arm Disarm 6 4 2 Define the DIN1 DIN2 type Eg 1234DIN2NO define the DIN2 as NO Normally Open type 6 4 3 Modify th...

Page 13: ...g Arm Disarm Status DIN1 2 status Relay status GSM signal value full is 31 cellular signal weak if lower than 14 AC DC power supply status Inquiry the self check and auto report time 6 5 3 Inquiry cur...

Page 14: ...n 100pcs RTU5025 only for small project we suggest client using PC software to configurate or read historical data via USB cable or SMS 6 6 1 Enable data function Disable data function 6 6 2 APN call...

Page 15: ...If the RTU5025 works but fail to send SMS texts switch the power off and on again after one minute Test it after few minutes later or ensure and check the settings are correct and the cellular signal...