_________________________________________________________________________________________
Page 7 of 15 King Pigeon Communication Co.,Limited. Ver 1.5 File No.:RTU5025103
A Professional GSM 3G M2M products manufacturer
and automation solution provider, since 2005.
www.GSM-Gate-Opener.com [email protected]
5. Setting
b
y PC software instructions (recommend):
1) Open the unit's back side cover and insert the SIM card.
2) Connect the unit's power supply.
3) Send SMS command to RTU5025 for adjust the time.
for example:
1234TEL001911#,
this step is MUST.
4) Connect the RTU5025 to computer by USB cable.
5) On
compurter’s desktop,right click
"My Computer" >>> "Property" >>>"Hardware" >>"Device Manager"
.
6) Find "
Ports (COM & LPT)
",check the port number of "
Silicon Labs CP210x USBto UART Bridge
",
for example:COM3. (
Click here
to know
how to find out the COM Port on your computer
)
7) Run this configurate software,select the COM Port number,for example:COM3.click"Open",the downside
"COM Port" status indicates to Green,connection successful.
8) Click "Log in",default password is 1234. Fill the new password if you had changed before.
9) Click "Read Settings". Configurate the parameters as per you need.
10) Click "Save Settings".
11) After finished the configuration,disconnect the USB cable,restart the unit for enter to working status.
1) Basic settings
Read Settings:
Read the basic parameter settings from RTU5025 to PC software.
Save Settings:
Save the basic parameter settings to the RTU5025.
Import profile:
Import .xls profile, this can use for a number of RTU5025 with similar settings.
Export profile:
Export the parameter settings as .xls format to the PC,under the /configuration folder.
pwdTELphone number of the RTU5025#