![Kinco HP043-20DT User Manual Download Page 48](http://html1.mh-extra.com/html/kinco/hp043-20dt/hp043-20dt_user-manual_1967647048.webp)
Kinco-HP
User Manual
48
2) Set SMW68 according to desired cycle time.
3) Execute the
PLS
instruction to configure PTO0 and start it, then a new PTO with the
updated cycle time shall be generated.
Changing the PTO Pulse Number(Single-Segment Operation)
Follow these steps to change the PTO pulse count:
1) Set control byte SMB67 according to the desired operation.
For example, SMB67 = B#16#84 indicates:
Enable the PTO/PWM function
Select PTO operation
Select 1μs as the time base
Allow updating the pulse number
2) Set SMD72 according to desired pulse number.
3) Execute the
PLS
instruction to configure PTO0 and start it, then a new PTO with the
updated pulse number shall be generated.
Execute the PTO (Multiple-Segment Operation)
1) Set control byte SMB67 according to the desired operation.
For example, SMB67 = B#16#A0 indicates:
Enable the PTO/PWM function
Select PTO operation
Select multi-segment operation
Select 1μs as the time base
2) Set an odd number as the starting position of the profile table into SMW168.
3) Use V area to configure the profile table.
4) (Optional) Use ATCH to attach the PTO0-complete event (event 28) to an interrupt
routine to respond in real time to a PTO0-complete event.
Summary of Contents for HP043-20DT
Page 8: ...Kinco HP User Manual 8 1 4 4 Dimension Dimension 132 102 40 1mm Cutout size 119 93mm...
Page 22: ...Kinco HP User Manual 22...
Page 23: ...Kinco HP User Manual 23...
Page 25: ...Kinco HP User Manual 25...
Page 27: ...Kinco HP User Manual 27 3 Click update and recovery in the PC settings...
Page 28: ...Kinco HP User Manual 28 4 Click restart now at advanced startup 5 Click advanced options...
Page 29: ...Kinco HP User Manual 29 6 click startup settings 7 Click restart...
Page 31: ...Kinco HP User Manual 31 10 Figure as below after successful...