23
Max. sampling
time set value
(MAX.t)
1. Setting example: When the displayed value exceeds the
LCUT, the maxi. sampling function activates. Modifiable
range: 0 ~ 99 seconds.
2. Press
to enter parameter modification, press
or
to modify the value.
3. Press ENT to save the modified parameters and enter the
next parameter setting page.
* Set 0 seconds: Continuous max. sampling
* This parameter setting shall be used in conjunction with
the display of the lowest cut setting (LCUT).
Zero stable range
thousandths set
value
(Zb)
Setting example: (Zb modifiable range: 0 ~ 9.999)
1. Input 4-20mA, display 0-600.0bar, the required stable
number is 1.0bar. Stable range is ±1bar at zero point.
Expression:
(
Thousandths)
Required stable number ÷ Max. number of input displays
×
1000 = Zb
1.0
600.0
1000 = 1.666 (Zb)
2. When the displayed value returns to zero as the stable
range, the zero point is automatically stabilized.
Zero tracking time
set value
(Zbt)
Setting description:
1. After the displayed value enters Zb stable tracking
range, the tracking compensation will be performed
through this set time. Modifiable time: 0 ~99 second.
2. Press
to enter parameter modification, press
or
to modify the value.
3. Press ENT to save the modified parameters and enter the
next parameter setting page. This function must be used
with Zb.
Input stable range
thousandths set
value
(Hb)
Setting example: (Hb modifiable range: 0 ~ 9.999)
1. Input 4-20mA, display 0-600.0bar, the required stable
number is 0.5bar. Stable range is 0.5bar at input value.
Expression:
(
Thousandths)
0.5 ÷ 600.0
×
1000 = 0.833 (Hb)
2. The displayed value enters the stable range and
automatically stabilizes the displayed value.
Input tracking time
set value
(Hdt)
Setting description:
1. After the displayed value enters Hb stable tracking
range, the tracking compensation will be performed
through this set time. Modifiable time: 0 ~99 second.
2. Press
to enter parameter modification, press
or
to modify the value.
3. Press ENT to save the modified parameters and enter the
next parameter setting page.
* This function must be used with Hb.
Display scale
setting value
(FiLt)
1. Setting example: Modifiable range: 0, 1, 2, 5
If it is set to 1, the single digit is displayed as 1, 2, 3, 4
(normal display)
If it is set to 2, the single digit is displayed as 2, 4, 6, 8
(even display)
If it is set to 5, the single digit is displayed as 0, 5 (display
in the multiple value of 5)
If it is set to 0, the single digit is displayed as 0 (10 digits
display)
Display overflow
setting value
(DoFLv.)
1. Setting example: Basic unit forward display is up to
1000. Need 1100 to display overflow. Set to 1100 here.
Modifiable range: 0 ~999999.
2. Press
to enter parameter modification, press
or
to modify the value.
3. Press ENT to save the modified parameters and enter the
next parameter setting page.
* This parameter setting shall be used in conjunction with
the basic unit setting group.
Summary of Contents for KTM-IWT400
Page 6: ...5 配線圖 2 1操作流程及顯示 ...
Page 30: ......