20
Forward highest
display setting
value
(r.dSPM)
1. Setting example: LOAD CELL inputs signal at the forward
highest shall display 1000. Set it to 1000 here. Modifiable
range: -199999 ~ 999999.
2. Press
to enter parameter modification, press
or
to
modify the value.
3. Press ENT to save the modified parameters and return to the
display value setting page.
* Press the Z key on this page to correct the forward highest
input signal. (Suitable for load cell)
Reverse 2nd
point display
setting value
(L.dSPM)
1. Setting example: LOAD CELL inputs signal at the reverse
2nd point shall display -500. Set it to -500 here. Modifiable
range: -199999 ~ 999999.
2. Press
to enter parameter modification, press
or
to
modify the value.
3. Press ENT to save the modified parameters and return to the
display value setting page.
* Press the Z key on this page to correct the reverse 2nd point
input signal. (Suitable for load cell)
Reverse highest
display setting
value
(L.dSPM)
1. Setting example: LOAD CELL inputs signal at the reverse
highest shall display -1000. Set it to -1000 here. Modifiable
range: -199999 ~ 999999.
2. Press
to enter parameter modification, press
or
to
modify the value.
3. Press ENT to save the modified parameters and return to the
display value setting page.
* Press the Z key on this page to correct the reverse highest
input signal. (Suitable for load cell)
2.4
Analog Output Setting Group
** In the normal display screen, press
for 3 seconds to enter the display of analog output setting group
Display Screen
Default
Screen Name
Modify Parameters and Process Description
Lowest analog
output deviation
correction value
(AoFSt)
1. Output zero point correction example: rated output is 0V,
the actual output is 0.2V, use
or
to fine-tune to 0V.
Modifiable range: -199999 ~ 999999.
2. Press
to enter parameter modification, press
or
to
modify the value.
3. Press ENT to save the modified parameters and enter the
next parameter setting page.
* Shift left to higher digits, the wider the adjustment range.
Highest analog
output deviation
correction value
(AGAin)
1. Setting example: LOAD CELL inputs signal at the reverse
highest shall display -1000. Set it to -1000 here. Modifiable
range: -199999 ~ 999999.
2. Press
to enter parameter modification, press
or
to
modify the value.
3. Press ENT to save the modified parameters and enter the
next parameter setting page.
* Shift left to higher digits, the wider the adjustment range.
Lowest analog
output
corresponding
display setting
value
(AnLo)
Setting example:
1. When the need the basic unit to display 4.0 and the output
is 4mA, modify it to 4.0 here. Modifiable range: -199999 ~
999999.
2. Press
to enter parameter modification, press
or
to
modify the value.
3. Press ENT to save the modified parameters and enter the
next parameter setting page.