![Kiefer INDUSAIL SONIC air Technical Information Download Page 12](http://html1.mh-extra.com/html/kiefer/indusail-sonic-air/indusail-sonic-air_technical-information_1966469012.webp)
Kiefer Klimatechnik GmbH
www.kieferklima.de/en
INDUSAIL SONIC active acoustic sail system
Technical modifications reserved
- E1909_08/21
PART I-12
INDUSAIL SONIC TECHNICAL DATA
INDUSAIL SONIC - types
plus
air
silent
DIMENSIONS
Standard - L x W x H
mm
2500 x 1100 x 255 2500 x 1100 x 250
2500 x 1100 x 50
Total weight in operation
kg
74
50
30
acoustic surface area
mm
2400 x 1000
2400 x 1000
2400 x 1000
Connector diameter
mm
1 x DN125
2 x DN160
-
SAIL
Acoustic mat
-
100 % polyester
100 % polyester
100 % polyester
Building material class (DIN EN 13501)
-
B-s1, d0
B-s1, d0
B-s2, d0
Colour of the circumferential profile
-
Natural anodised
Air diffuser profile
-
Black powder coated
VENTILATION / AIR CONDITIONING
Secondary air – filter cell (DIN EN ISO 16890)
-
ISO Coarse 60%
-
-
Centrally preconditioned outdoor air flow rate
m³/h
0 to 120
0 to 500
-
Max. primary cooling capacity
W
400
1600
-
Max. secondary cooling capacity
W
1250
-
-
Max. total cooling capacity
W
1600
1600
-
Nominal water flow rate; pressure drop
kg/h;
kPa
300; 21
-
-
Water connection
inch
½’’ male thread
-
-
ACOUSTIC ABSORBER
Sound absorption class (DIN EN ISO 354; DIN EN ISO 11654)
-
C
C
A
Assessed sound absorption level α
W
(DIN EN ISO 354;
DIN EN ISO 11654)
-
0.6
0.6
0.9
Recommended suspension height for optimum effect
mm
200 to 300
200 to 300
100 to 400
ELECTROTECHNICAL DATA
Mains connection
V/Hz
230/50
-
-
IP rating of secondary air cooling unit (motor/electronics)
-
IP 44/20
-
-
Nominal power consumption of the fan at control voltage 10 V/6 V
W
45/22
-
-
CONTROL
Control voltage of fan DC
V
0–10
-
-
Control voltage of optional actuator for heat exchanger DC
V
0–10
-
-