background image

•  In very humid areas. Moisture or steam can cause nuisance alarms.

•  In insect-infested areas.

•  Smoke alarms should not be installed within 3 ft (.9m) of the follow-

ing: the door to a kitchen, the door to a bathroom containing a tub or 
shower, forced air supply ducts used for heating or cooling, ceiling or 
whole house ventilating fans, or other high air flow areas.

•  Kitchens. Normal cooking may cause nuisance alarms. If a kitchen 

alarm is desired, it should have an alarm silence feature or be a pho-
toelectric type.

•  Near fluorescent lights. Electronic “noise” may cause nuisance 

alarms.

•  Smoke alarms are not to be used with detector guards unless the 

combination (alarm and guard) has been evaluated and found suit-
able for that purpose.

3. INSTALLATION  INSTRUCTIONS

WIRING REQUIREMENTS

•  This smoke alarm should be installed on a U.L. listed or recog-

nized junction box. All connections should be made by a quali-
fied electrician and all wiring used shall be in accordance with 
articles 210 and 300.3(B) of the U.S. National Electrical Code 
ANSI/NFPA 70, NFPA 72 and/or any other codes having jurisdic-
tion in your area. The multiple station interconnect wiring to 
the alarms must be run in the same raceway or cable as the AC 
power wiring. In addition, the resistance of the interconnect wir-
ing shall be a maximum of 10 ohms.

•  The appropriate power source is 120 Volt AC Single Phase sup-

plied from a non-switchable circuit which is not protected by a 
ground fault interrupter.

• 

WARNING:

 This alarm cannot be operated from power derived 

from a square wave, modified square wave  or modified sine 
wave inverter. These types of inverters are sometimes used to 
supply power to the structure in off grid installations, such as 
solar or wind derived power sources. These power sources pro-
duce high peak voltages that will damage the alarm.

WIRING INSTRUCTIONS FOR AC QUICK CONNECT HARNESS

CAUTION! TURN OFF THE MAIN POWER TO THE CIRCUIT 
BEFORE WIRING THE ALARM.

•  For alarms that are used as single station, DO NOT CONNECT 

THE RED WIRE TO ANYTHING. Leave the red wire insulating cap 

1475-7205-00(820-0905-EN)_R1.indd   5

1475-7205-00(820-0905-EN)_R1.indd   5

2009.12.9   10:07:37 AM

2009.12.9   10:07:37 AM

Summary of Contents for PI 2000

Page 1: ...We know you expect nothing less when the lives of your family are at stake Kidde alarms and accessories CAN ONLY BE interconnected with other Kidde alarms and accessories as well as specified brands a...

Page 2: ...S BEFORE INSTALLATION AND KEEP THIS MANUAL NEAR THE ALARM FOR FUTURE REFERENCE CONTENTS OF THIS MANUAL 1 RECOMMENDED LOCATIONS FOR SMOKE ALARMS 2 LOCATIONS TO AVOID 3 INSTALLATION INSTRUCTIONS 4 OPERA...

Page 3: ...ing the alarm on the wall use an inside wall with the top edge of the alarm at a minimum of 4 10 cm and a maximum of 12 30 5 cm below the ceiling see figure 1 Put smoke alarms at both ends of a hall w...

Page 4: ...walls and roof This may create a thermal bar rier which can prevent the smoke from reaching an alarm mounted on the ceiling In such units install the smoke alarm on an inside wall with the top edge o...

Page 5: ...B of the U S National Electrical Code ANSI NFPA 70 NFPA 72 and or any other codes having jurisdic tion in your area The multiple station interconnect wiring to the alarms must be run in the same race...

Page 6: ...FM I KN COSM IB HD135F KN COB IC KN COP IC KN COPF I and FireX models AD ADC FADC with models without battery backup Kidde models 1235 i12020 KN COSM I 120X SM120X CO120X SL177 be advised that the mo...

Page 7: ...and wiring the AC QUICK CONNECT harness as described in the WIRING INSTRUCTIONS attach the trim ring to the electrical box see figure 6 3 Pull the AC QUICK CONNECTOR through the center hole in the tr...

Page 8: ...the base is allowed to engage the mounting bracket Rotate the alarm onto the trim ring until you hear the tamper resist tab snap into place locking the alarm on the trim ring Using the tamper resist...

Page 9: ...present The HUSH feature can be used repeatedly until the air has been cleared of the condition causing the alarm NOTE DENSE SMOKE WILL OVERRIDE THE HUSH CONTROL FEATURE AND SOUND A CONTINUOUS ALARM C...

Page 10: ...est button on any one of the interconnected alarm is pressed If no alarm sounds the unit has defective batteries or other failure DO NOT use an open flame to test your alarm you could damage the alarm...

Page 11: ...RY INSTALLATION AND REMOVAL To replace or install the batteries you must first remove the alarm from the trim ring by following the ALARM REMOVAL instructions at the beginning of this section After al...

Page 12: ...er hose and blowing or vacuuming through the openings around the perimeter of the alarm The outside of the alarm can be wiped with a damp cloth After cleaning reinstall your alarm and test your alarm...

Page 13: ...m protection a smoke alarm should be installed in each sleeping area on every level of a home Although smoke alarms can help save lives by providing an early warning of a fire they are not a substitut...

Page 14: ...t of a radioactive element in the sensing chamber to enable detection of visible and invisible combustion products The radioac tive element is safely contained in the chamber and requires no adjustmen...

Page 15: ...69 NOTIFY YOUR LOCAL FIRE DEPARTMENT AND INSURANCE COMPANY OF YOUR SMOKE ALARM INSTALLATION 11 CAUTION AS REQUIRED BY THE CALIFORNIA STATE FIRE MARSHAL Early warning fire detection is best achieved by...

Page 16: ...CASE EXCEED THE COST OF REPLACEMENT OF SMOKE ALARM AND IN NO CASE SHALL KIDDE OR ANY OF ITS PARENT OR SUBSIDIARY CORPORATIONS BE LIABLE FOR CONSEQUENTIAL LOSS OR DAMAGES RESULTING FROM THE FAILURE OF...

Reviews: