LINEAR OPTICAL REFLECTING BEAM  SMOKE DETECTOR

 

 

 

SF

 5P70 

distance: min 10m to max 70m

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 
 
 
 
 
 
 

 
 
 

 
 
 
 
 
 

 

 
 
 
 
 
 
 

ATTENTION

 

 

MODEL REQUIRES INTERFACE INT8BA  

Before installing the detectors, check the wall or surfaces on which the TRX brackets and retroreflector or swivel are 
mounted. They must not be in any way subjected to movement or vibrations during the operation of the units. 
Before installing the units check whether there are any shiny or reflective surfaces crosswise between the beams along the 
IR beam path between the TRX and the retroreflector. If there are, check whether they interfere with the retroreflector re-
sponse. If a part of IR light is reflected back by surfaces other than the retroreflector, different  TRX positions should be 
selected.  
Do not place this model of detector in warehouses where the goods stored are closer than 1,20m to the ceiling or roof. 
Keep the whole path whole detector path  distance between the TRX and reflector device as clear as possible. 
Avoid detector placement in front of or near to strong electric lights or bright sunlight. 
If the installed distance between TRX and retroreflector is between 10m and 50m insert the indicated diaphragm that is 
included as accessories (cod DC60-4B) in the package as shown in the below table form.

 

 

RILEVAZIONE ELETTRONICA ANTINCENDIO 

37138 VERONA - Via F. Da Levanto 14 - b 

Tel. +39 - 0458347777    Fax +39 - 0458347778 

E-mail: [email protected] 

www.setronicverona.com 

70m MAX 

TRX 

STRxBSF 

REFLEX 

K40 

»

220 mm

¼

 

»

148 mm

¼

 

»

126 mm

¼

 

»

178 mm

¼

 

RETROREFLECTOR 

100 mm 

100 m

m

 

DIAPHRAGM 

 

KIT DIAPHRAGMS cod. 

DC60-4B 

)

 

Cod. DIAPGHRAGM 

OPERATING DISTANCE 

DC6008B > 

10 

 20m 

DC6014B > 

20 

 30m 

DC6018B > 

30 

 40m 

DC6030B > 

40 

 50m 

Ø HOLE 

8 mm 

14 mm 
18 mm 
30 mm 

)

 

)

 

)

 

)

 

ARTICULATED BRACKET cod. 

SM 

(OPTIONAL) 

Summary of Contents for BOOMERANG 5P70

Page 1: ...odel of detector in warehouses where the goods stored are closer than 1 20m to the ceiling or roof Keep the whole path whole detector path distance between the TRX and reflector device as clear as possible Avoid detector placement in front of or near to strong electric lights or bright sunlight If the installed distance between TRX and retroreflector is between 10m and 50m insert the indicated dia...

Page 2: ...H in the horizontal plane to the right until the yellow led 3 stops flash ing and goes out Counting the knob s rotations turn back the knob to the left turning and counting until the yellow led F stops flashing and goes out During operation the red flashing Smoke led can light up as in alarm This is normal Reset by removing the connector to the TRX for min 3 seconds 6 Divide the number of turns tw...

Page 3: ...threshold at 450 divisions Contact our technical services if you wish to raise this level above 450 divisions f Switch OFF and disconnect the UTA Jack plug store the instrument in a cool place dry with its batter ies removed CALIBRATION PROVIDED BY ADM DEVICE AND MULTIMETER If an ADM is being used a Insert the ADM jack plug in the TRX socket Switch on ADM and select detector mode Insert the ADM s ...

Page 4: ...N 2 Delay 30 POSITION 3 Delay 60 POSITION 4 Delay 90 1 2 3 4 5 6 7 8 24V GND NO C NC NO C NC TERMINALS NOT USED IN BOOME RANG MODELS 104 mm 130 mm 104 mm 130 mm inserted not inserted RRX ABSORBTION MAX 24 VOLT interface included mA MAX JB IN JB OUT NORMAL WORKING 80 94 TROUBLE 108 94 ALARM 100 114 www setronicverona com LINE LINE ...