2-9
November 2002
06-235975-001
Kidde Gemini II System
OptRyIsoFAIL
Optional relay isolation failure.
Prog Rel ISO
MCP programmable relay isolated.
PSU FLT
Power supply failure
.
RegisterFAIL
The operator is trying to register a Re-
mote Hazard or Remote Display Unit,
but the registration has failed.
ReleaIsoFAIL
Release isolation failure.
Release FLT
Fault on agent release output circuit.
Release ISO
Agent release output has been iso-
lated.
Release/Sla.
MCP has activated its agent release
at the request of a stop valve control
slave.
Releasing
Agent release circuit is activated and
releasing agent to the hazard.
Reset
RESET button was pressed on the
front panel of one of the units.
Reset by MCP
Unit was reset from the Main Control
Panel.
Snd1 LoadFLT
Sounder 1 is drawing too much cur-
rent.
Snd1 o/c FLT
Sounder 1 is open circuit.
Snd1 s/c FLT
Sounder 1 is short circuit.
Snd2 LoadFLT
Sounder 2 is drawing too much cur-
rent.
Snd2 o/c FLT
Sounder 2 is open circuit.
Snd2 s/c FLT
Sounder 2 is short circuit.
Sounder ISO
Indicating (sounder) output circuit has
been isolated.
Stp/valvFAIL
Failure to update an RHU with its stop
valve control status.
S/valv FLT
Stop valve output fault.
Superv FLT
Fault on the supervisory input circuit.
Supervisory
Supervisory input received.
Suprv IP ISO
Supervisory input circuit has been iso-
lated by the operator.
Supv IsoFAIL
Supervisory isolation failure.
Switch FLT
RDU has detected abort/manual re-
lease switches but is configured not to
have them.
Trbl Rel ISO
MCP trouble relay has been isolated
by the operator.
Unregistered
The Main Control Panel is communi-
cating with a Remote Hazard Unit, but
the unit is not registered.
Update FAIL
The Main Control Panel could not get
an update of events from the Remote
Hazard or Remote Display Unit.
W/F loop FLT
Break in waterflow wiring loop on a
Style D circuit.
W/Flo IP ISO
Waterflow input has been isolated by
the operator.
W/Flow FLT
Fault on the waterflow input circuit.
W/T Abort
Abort activated during walk test.
W/T Man.Rel.
Manual release activated during walk
test.
W/T Superv.
Supervisory activated during walk test.
W/T W/Flow
Waterflow input activated during walk
test.
W/T Zone 1
Zone 1 detectors activated during walk
test.
W/T Zone 2
Zone 2 detectors activated during walk
test.
WalkTestFAIL
Failure to correctly begin a walk test.
Waterflow
Release circuit is activating the sprin-
kler system.
Wflo IsoFAIL
Failure to isolate waterflow input on an
RHU.
Zn1 Loop FLT
Break in Zone 1 wiring loop on Style D
circuit.
Zn2 Loop FLT
Break in Zone 2 wiring loop on a Style
D circuit.
Zone 1 FLT
Zone 1 detectors open circuit.
Zone 2 FLT
Zone 2 detectors open circuit.