background image

9

Symptom

1. Green L.E.D. not lit

2. Frequent nuisance

alarms

3. Alarm chirps every 30-40

seconds

4. Alarm does not sound

when test button pressed
and held.

5. Interconnected alarms

do not sound when test
button is pressed and
held.

Possible cause/solutions

a. Loss of mains power – check at Consumer Unit for

Blown Fuse or tripped Circuit Breaker.

b. Check cables at back of alarm are correctly seat-

ed

/wired in and the alarm is pushed fully home.

(see “Battery Changing” section).

See sections 2,3,4 and 7. If sited incorrectly/not regu-
larly cleaned as section 11, nuisance alarms can
occur.

Verify green LED is lit continuously the see section 5
to replace battery if applicable. If unit has rechargeable
battery or problem persists after installing a new bat-
tery, contact customer service.

See parts 1a and 1b above. Have installer re check
wiring if Green LED is illuminated, but alarm does not
appear to function. If no Green LED check consumer
unit. Alarm will still function on battery power, if battery
is in serviceable state. <Red LED will blink about once
a minute to confirm>. Check via Test Button.

See section 4 above – consult a qualified  electrician
or your Landlord to remedy as soon as possible.

15. Troubleshooting

Always turn off the mains supply to AC alarms before checking connections etc..

Consult our website for additional information and help
www.smoke-alarms.co.uk

1385-7206-00_R3_V9:-  2011.3.14  5:28 PM  Page 9

Summary of Contents for Fyrnetics Slick 1SFW

Page 1: ...en Way Colnbrook SL3 0HB UK www kiddefyrnetics co uk Kidde Fyrnetics 2008 Electrical rating 230V AC 50Hz 80mA max per alarm maximum 80mA for originating unit with 24 Devices inter connected These alarms may be used with the Kidde Wireless base accesso ry enabling interconnection between alarms wirelessly The Remote Test Hush accessory will also work with alarms on Wireless bases 1385 7206 00 Conte...

Page 2: ...Doing so before hand can cause serious injury Do not install in a dripping water splashing very humid area WARNING This alarm cannot be operated from power derived from a square wave or modified sine wave inverter These types of inverters are sometimes used to sup ply power to the structure in off grid installations such as solar or wind derived power sources These power sources produce high peak ...

Page 3: ...ansferred from the outside to the inside through poorly insulated walls and roof This may create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling If you are not sure about the insulation in your home or if you notice that the outer walls and ceiling are either hot or cold install the alarm on an inside wall In such homes install the smoke alarm with the t...

Page 4: ... 3ft of the following the door to a kitchen the door to a bathroom containing a tub or shower ceiling or whole house ventilat ing fans orother high air flow areas Kitchens Normal cooking may cause nuisance alarms Only Heat Alarms are suitable for use in Kitchens they should also be fitted in integral garages Smoke alarms are not to be used with detector guards unless the combination alarm and guar...

Page 5: ...lace cover by locating leg as shown and then gently levering clip to full close If necessary the alarm can be unclipped from its base plate by depressing where shown Figure b above and just the base installed at 1st fix The alarm can then be slid on to the hinge and then slid home as illustrated below 2 d 5 Loose Battery Models The alarm will not locate without a battery in the compartment Never r...

Page 6: ...Smoke Alarms and or 18 Alarms total Smoke Heat CO and etc With 18 alarms interconnected up to 6 alarm accessories relay modules visual signaldevice and etc Crossing line and neutral connections or line and interconnect connections will fatally damage all interconnected alarms invalidating the guarantee All interconnected alarms must be powered off the same fuse circuit breaker Total cable length b...

Page 7: ... interconnected only triggering alarm will have this state If interconnected to other alarms only the triggering alarm will have a rapidly flashing L E D On optical alarms if the red L E D blinks every 30 40 seconds and the alarm chirps in between it indicates failure of the sensing chamber Householders should consult Owner s Manual or installer landlord The alarm sounder and flashing L E D will r...

Page 8: ...tification to occupants of the need to escape followed by the appropriate egress actions by those occupants Fire warning systems for dwelling units are capable of protecting about half of the occupants in potentially fatal fires Victims can be involved with the fire too old or young or physically or mentally impaired such that they cannot escape even when warned early enough that escape should be ...

Page 9: ...ontinuously the see section 5 to replace battery if applicable If unit has rechargeable battery or problem persists after installing a new bat tery contact customer service See parts 1a and 1b above Have installer re check wiring if Green LED is illuminated but alarm does not appear to function If no Green LED check consumer unit Alarm will still function on battery power if battery is in servicea...

Page 10: ...y Colnbrook SL3 0HB UK The terms of this guarantee will not apply in the following circumstances If alarm has been damaged modified neglected dismantled contaminated abused or altered after the date of purchase or if it fails to operate due to incorrect selection siting installation maintenance or inadequate AC or DC electrical power or damage caused by failure to abide by the instructions supplie...

Reviews: