When mounting the alarm on the wall, use an inside wall with the top edge of the detection ele-
ment a minimum of 15cm (6”) and a maximum of 30cm (12”) below the ceiling, and at least 61cm
(2 feet) from any inside corner (see DIAGRAM A).

Install smoke alarms on sloped, peaked or cathedral ceilings at or within 0.9m (3ft) of the
highest point (measured horizontally). Smoke alarms in rooms with ceiling slopes greater than
0.3m in 2.4m (1 foot in 8 feet) horizontally shall be located on the high side of the room. A row
of detectors shall be spaced and located within 0.9m (3ft) of the peak of the ceiling measured
horizontally.(see DIAGRAM "C")

Put smoke alarms at both ends of a bedroom hallway or large room if the hallway or room is

more than 9.1m (30 feet) long.

In homes that are not well insulated, extreme heat or cold can be transferred from the outside
to the inside through poorly insulated walls and roof. This may create a thermal barrier which
can prevent the smoke from reaching an alarm mounted on the ceiling. If you are not sure
about the insulation in your home, or if you notice that the outer walls and ceiling are either
hot or cold, install the alarm on an inside wall. In such homes, install the smoke alarm with the
top edge of the alarm at 15cm (6”) and a maximum of 30cm (12”) below the ceiling,

Install Smoke Alarms on tray-shaped ceilings (coffered ceilings) on the highest portion of the
ceiling or on the sloped portion of the ceiling within 30cm (12”) vertically down from the
highest point (see DIAGRAM "D").

3

300mm (12")

1

50mm (6")

Dead

Air

Living Room

Bedroom

Bedroom

Bathroom

Kitchen

Garage

Loft Conversion

Heat Alarm

Ion Alarm

Do not fit

Optical Alarm

DIAGRAM “A”

DIAGRAM “C”

DIAGRAM “D”

SINGLE FLOOR PLAN

MULTI FLOOR PLAN

DIAGRAM “B”

100mm

NOT IN THIS AREA

ANYWHERE ALONG 
THIS BOLD SURFACE

30cm

(12”)

1385-7206-00_R3_V9:-  2011.3.14  5:28 PM  Page 3

Summary of Contents for Fyrnetics Slick 1SFW

Page 1: ...en Way Colnbrook SL3 0HB UK www kiddefyrnetics co uk Kidde Fyrnetics 2008 Electrical rating 230V AC 50Hz 80mA max per alarm maximum 80mA for originating unit with 24 Devices inter connected These alarms may be used with the Kidde Wireless base accesso ry enabling interconnection between alarms wirelessly The Remote Test Hush accessory will also work with alarms on Wireless bases 1385 7206 00 Conte...

Page 2: ...Doing so before hand can cause serious injury Do not install in a dripping water splashing very humid area WARNING This alarm cannot be operated from power derived from a square wave or modified sine wave inverter These types of inverters are sometimes used to sup ply power to the structure in off grid installations such as solar or wind derived power sources These power sources produce high peak ...

Page 3: ...ansferred from the outside to the inside through poorly insulated walls and roof This may create a thermal barrier which can prevent the smoke from reaching an alarm mounted on the ceiling If you are not sure about the insulation in your home or if you notice that the outer walls and ceiling are either hot or cold install the alarm on an inside wall In such homes install the smoke alarm with the t...

Page 4: ... 3ft of the following the door to a kitchen the door to a bathroom containing a tub or shower ceiling or whole house ventilat ing fans orother high air flow areas Kitchens Normal cooking may cause nuisance alarms Only Heat Alarms are suitable for use in Kitchens they should also be fitted in integral garages Smoke alarms are not to be used with detector guards unless the combination alarm and guar...

Page 5: ...lace cover by locating leg as shown and then gently levering clip to full close If necessary the alarm can be unclipped from its base plate by depressing where shown Figure b above and just the base installed at 1st fix The alarm can then be slid on to the hinge and then slid home as illustrated below 2 d 5 Loose Battery Models The alarm will not locate without a battery in the compartment Never r...

Page 6: ...Smoke Alarms and or 18 Alarms total Smoke Heat CO and etc With 18 alarms interconnected up to 6 alarm accessories relay modules visual signaldevice and etc Crossing line and neutral connections or line and interconnect connections will fatally damage all interconnected alarms invalidating the guarantee All interconnected alarms must be powered off the same fuse circuit breaker Total cable length b...

Page 7: ... interconnected only triggering alarm will have this state If interconnected to other alarms only the triggering alarm will have a rapidly flashing L E D On optical alarms if the red L E D blinks every 30 40 seconds and the alarm chirps in between it indicates failure of the sensing chamber Householders should consult Owner s Manual or installer landlord The alarm sounder and flashing L E D will r...

Page 8: ...tification to occupants of the need to escape followed by the appropriate egress actions by those occupants Fire warning systems for dwelling units are capable of protecting about half of the occupants in potentially fatal fires Victims can be involved with the fire too old or young or physically or mentally impaired such that they cannot escape even when warned early enough that escape should be ...

Page 9: ...ontinuously the see section 5 to replace battery if applicable If unit has rechargeable battery or problem persists after installing a new bat tery contact customer service See parts 1a and 1b above Have installer re check wiring if Green LED is illuminated but alarm does not appear to function If no Green LED check consumer unit Alarm will still function on battery power if battery is in servicea...

Page 10: ...y Colnbrook SL3 0HB UK The terms of this guarantee will not apply in the following circumstances If alarm has been damaged modified neglected dismantled contaminated abused or altered after the date of purchase or if it fails to operate due to incorrect selection siting installation maintenance or inadequate AC or DC electrical power or damage caused by failure to abide by the instructions supplie...

Reviews: