Installation and Maintenance
June 2020
2-4
P/N 06-237620-001
2-6
MAINTENANCE PROCEDURES
A program of systematic maintenance is essential for continuous, proper operation of all Natura
IGS Systems. Follow a periodic maintenance schedule as outlined in Table 2-1. Additionally,
have an Authorized Natura IGS Systems Distributor perform preventative maintenance as
outlined in Table 2-2.
If areas of rust or corrosion are found during the inspection of cylinders contact your
Authorized Natura IGS Systems Distributor for further examination.
2-6.1
Preventative Maintenance Schedule
As an owner, perform preventative maintenance per Table 2-1.
WARNING
Natura IGS cylinders and components must be handled, installed, inspected
and serviced only by qualified and trained personnel in accordance with the
instructions contained in this manual and Compressed Gas Association (CGA)
pamphlets C-1, C-6 and P-1. CGA pamphlets my be obtained from the
Compressed Gas Association website:
Table 2-1. Owner Preventive Maintenance Schedule
Schedule
Requirement
Paragraph
Weekly
Inspect Natura IGS cylinder and check the cylinder pressures
Check nitrogen pilot cylinder pressures
Perform hazard and enclosure inspection
Perform pipework and controls inspection
Monthly
Perform Weekly Inspection as outlined in Section 2-7
and the following additional tasks:
Perform General Inspection
Inspect Hazard Access
Inspect Hoses
Inspect Release Units and Slave Gauges
Inspect Cylinder and Valve Assembly
Inspect Electric Control Heads