1-4.4
IG-55 (Nitrogen and Argon)
Natura IGS systems with IG-55 are fixed fire extinguishing systems that use an inert, gaseous
mixture of 50% Nitrogen and 50% Argon known as Argonite
®
, UN number of 1956.
Specification for IG-55 is an Argon/Nitrogen 50%/50% ratio by volume. Tolerance of mixture
in air is as follows:
•
Argon: 50% +/- 5%
•
Nitrogen: 50% +/- 5%
1-4.4.1
Purity of Argon and Nitrogen
Each element shall conform to the following purity specification:
Argon:
•
Argon greater than or equal to 99.99%
•
Oxygen less than or equal to 10 ppm
•
Water less than or equal to 10 ppm
Nitrogen:
•
Nitrogen greater than or equal to 99.7%
•
Oxygen less than or equal to 10 ppm
•
Water less than or equal to 10 ppm
Note:
Only principal contaminants are shown. Other measurements may include: Carbon
Monoxide, Carbon Dioxide, Nitrogen Oxide, and Nitrogen Dioxide most < 20 ppm.
Figure 1-9. IG-55 Pressure/Temperature Curve Isometric Diagram for 200 bar, U.S. Customary Units