General Information
P/N 06-237620-001
1-7
June 2020
1-4.3
IG541 (Nitrogen, Argon, and Carbon Dioxide)
Natura IGS systems with IG-541 are fixed fire extinguishing systems that use an inert gaseous
mixture of 52% Nitrogen, 40% Argon, and 8% Carbon Dioxide (IG-541), UN number 1956.
Specification for IG-541 is a Nitrogen/Argon/Carbon Dioxide 52%/40%/8% ratio by volume.
The tolerance of the mixture in air is as follows:
•
Nitrogen: 52% +/- 4 %
•
Argon: 40% +/- 4%
•
Carbon Dioxide: 8% + 1%/ - 0%
1-4.3.1
Purity
Each element shall conform to the following purity specification:
Argon:
•
Argon greater than or equal to 99.99%.
•
Oxygen less than or equal to 10 ppm.
•
Water less than or equal to 10 ppm.
Nitrogen:
•
Nitrogen greater than or equal to 99.7%
•
Oxygen less than or equal to 10 ppm.
•
Water less than or equal to 10 ppm.
Carbon Dioxide:
•
Carbon Dioxide greater than or equal to 99.7%
•
Oxygen less than or equal to 10 ppm.
•
Water less than or equal to 10 ppm.
Note:
Only principal contaminants are shown. Other measurements may include: Carbon
Monoxide, Carbon Dioxide, Nitrogen Oxide, and Nitrogen Dioxide most < 20 ppm.
Figure 1-5. IG-541 Pressure/Temperature Curve Isometric Diagram for 200 bar, U.S. Customary Units